96 NCB Service Manual
Version 1.0
Check method
Fault
Possible Causes
Check method
Dual Venturi
action error
Defective Dual
Venturi cable or
harness
1.
Disconnect all cables from the Dual Venturi.
2.
Using a multi-meter, test the Dual Venturi electrical wiring.
Dual Venturi not
operating
1.
Turn off the power to the unit using the main power switch (do not use the front
panel power button) and wait for 10 seconds.
2.
Turn on the power.
3.
Wait until Fan Auto Adjusting is complete.
4.
Enter the Dual Venturi Test Mode and perform a test.
1)
Repeat the test at least twice. Turning the unit ON and OFF once makes one test
cycle. ON
OFF
ON
OFF
…… is the minimum sequence.
2)
Confirm that the Dual Venturi is operating correctly.
a.
Listen to the Dual Venturi while it is running and check for operational noise
(clicks at unit ON and unit OFF).
b.
If operational noise cannot be heard because of ambient noise, disassemble
the Dual Venturi and perform a visual inspection.
5.
If error message (E060) occurs, replace the Dual Venturi.
6.
If a Dual Venturi error does not occur, replace the APS.

Table of Contents

Other manuals for Navien NCB-210

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Navien NCB-210 and is the answer not in the manual?

Navien NCB-210 Specifications

General IconGeneral
BrandNavien
ModelNCB-210
CategoryBoiler
LanguageEnglish

Related product manuals