5. TroubleshootingData
5.1. Error Code List
Reason
Error
Code
Self-diagnostic / Action Reset
E001
Manual
Water is boiling inside the heat
exchanger
1. Clean the inlet water strainer
(part #62);
2. Check the water adjustment valve
(part #16);
3. Check the heat exchanger;
flush with a cleaning solution
Manual
Ignition failure
1. Check to see if the main gas
supply valve is open.
2. Check the igniter for spark
(part #18).
E003
Automatic
False flame detection
1. Ensure ground wire is connected.
2. Check the igniter for spark.
E004
Automatic
Hot water outlet:
Thermistor -open
1. Check the Thermistor.
2. Check for loose connection
3. Replace the Thermistor.
E007
Automatic
Hot water outlet:
Thermistor -short
1. Check the Thermistor.
2. Look for short or water in connection
3. Replace the Thermistor.
E008
Manual
Abnormal fan motor activity
1. Check and clean the air filter1
(part #10).
2. Check and clean the fan motor
(part #21).
3. Check tower on board for loose connection
E009
Manual
Abnormal air pressure
1. Check the vent and fresh air pipe for
Obstructions.
2. Check and clean the air filter
(part #10).
3. Check hoses and condensate drain
E010
Manual
Flame loss
1. Check the main gas line (valve open?).
2. Check intake air pipe.
3. Check ground wire.
4. Check power supply.
5. Clean flame rod
E012
Manual
Abnormal PCB
1. Check power supply.
2. Check the power switch.
E015
Manual
Overheating of heat exchanger
1. Turn OFF the system for at least
30 minutes then restart;
2. Clean the inlet water strainer
(part #62).
3. Check the water adjustment valve(part #16)
4. Check the heat exchanger;
flush with a cleaning solution