Networkable VAV Controller
Specification and Installation Instructions
www.neptronic.com EVCB Standard Page | 10
TRIAC Outputs – Menu (3 of 6) | TO1 to TO4
On ( fan c ont inuously on )
Auto (fan follows demand )
TO1 DIR - RE V
DIR (direct )
REV (reverse)
PuLs (pulsed ) *
AO1
AO2
FLt (f loating )
CO2 (carbon dioxide )
Hr2 (heating ramp 2)
Hr1 (heating ramp 1)
TO4
TO3
TO2
Output Config
TO1
Cr2 (cooling ramp 2 )
Cr1 ( cooling ramp 1 )
TO1 Ramp
OFF
= scroll menu it ems
= select / set value
TO1 Close Pe rcent
40% (15-80%)
TO1 Signal Type
OnOf (on/off)
Go to "TO2"
* = Only if Hr1 or Hr2 is selected
TO1-TO2 F loating Time in Sec
100 sec (15 t o 250 /420 § secs)
TO1 Open Pe rc e nt
0% [0-(TO1 cls pos -4)]
Go to
"TO2"
TO2 DIR- RE V
DIR (direct )
REV (reverse )
PuLs (pulsed )
TO2 Close Percent
40% (15-80%)
TO2 Signal Type
OnOf (on/off)
Go to "TO3"
TO2 Ope n Perc ent
0% [0-(TO2 cls pos-4) ]
Go to
"TO3"
Main Menu Sub Menu Configuration
= scroll menu items
TO1 - TO2 DIR -REV
DIR (direct )
REV (reverse)
Go to
"TO3"
MSV.25
MSV.26
MSV.28
AV.77
AV.75
AV.79
AV.78
BV.32
BV.30
AV.80
BV.33
If CO
2
was selected
ầ
= Auto and On options
are for fan powered box
applications and are only
available with models:
- EVCB14NIT4S
- EVCB14NDT4S
- EVCB14NIT4SF
Go to "TO 2 Close Percent "
Go to "TO2 DIR-REV"
The number of Triac outputs
(TO) depend on the model .
S = motor/actuator.
TO(S) = None
T2(S) = 2
T4(S) = 4
TO1
On ( fan c ont inuously on )
Auto (fan follows demand )
CO2 (carbon dioxide )
Hr2 (heating ramp 2)
Hr1 (heating ramp 1 )
Cr2 (cooling ramp 2 )
Cr1 (cooling ramp 1)
TO2 Ramp
OFF
= select / set value
MSV.27
TO2
Go to "TO1 Close Percent "
Go to "TO1 DIR-REV"
OPt (Options )
Only available with CO
2
sensor models
Main Menu
APPS (Applications)
PrSs (Pressure)
rMp (Ramps)
NET (Network)
HrS (Time & D ate)
Setc (Settings)
Mot (Motor)
tMp (Temperature )
OutP (Outputs )
InPt (Inputs)
TO3 Open PercentTO3 Close Percent
TO3 DIR -REV
DIR (direct )
REV (reverse )
PuLs (pulsed ) *
FLt (float ing )
40% (15-80%)
TO3 Signal Type
OnOf (on/off)
Go to "TO4"
* = Only if Hr1 or Hr 2 is select ed
TO3-TO4 Floating Time in Sec
100 sec ( 15 to 250 /420 § sec s)
TO4 DIR -REV
DIR (direct)
REV (reverse)
PuLs (pulsed )
TO4 C lose Perce nt
40% (15-80%)
TO4 Signal Type
OnOf (on/off)
Go to "AO1"
TO4 Ope n Perc e nt
0% [0-(TO4 cls pos-4)]
Go to
"AO1"
TO3-TO4 DIR -REV
DIR(direct )
REV (reverse )
MSV.30
MSV.32
AV.81
AV.76
AV.83
AV.82
AV.84
BV.31
BV.34
BV.35
If CO
2
was selected
Go to " TO3 Close Percent "
Go to "TO3 DIR-REV"
Go to "TO 4 Close Percent "
Go to "TO4 DIR-REV"
On ( fan c ont inuously on )
Auto (fan follows demand )
CO2 (carbon dioxide )
Hr2 (heating ramp 2)
Hr1 (heating ramp 1)
Cr2 (cooling ramp 2 )
Cr1 ( cooling ramp 1 )
TO3 Ramp
OFF
= select / set value
MSV.29
TO3
On ( f an c ont inuously on )
Auto (fan follows demand )
CO2 (carbon dioxide )
Hr2 (heating ramp 2 )
Hr1 ( heating ramp 1)
Cr2 (cooling ramp 2 )
Cr1 (cooling ramp 1 )
TO4 Ramp
OFF
= select / set value
MSV.31
TO4
0% [0-( TO3 cls pos- 4)]
Go to
"TO 4 "
Go to
"AO1"
*** To save any changes , press on TRL and on TDU ***
*** To the previous step without saving, press on TRL and TDU ***