EasyManua.ls Logo

Neptronic EVCB14NIT2S - Page 11

Neptronic EVCB14NIT2S
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Networkable VAV Controller
Specification and Installation Instructions
www.neptronic.com EVCB Standard Page | 11
Analog Outputs – Menu (4 of 6) | AO1 and AO2
StFl (stpnt airflow 0-10 Vdc)*
AO1 DIR- REV
DIR (dir ec t )
REV (reverse)
CO2 (carbon dioxide)
Hr2 (heating ramp 2)
Hr1 (heating ramp 1)
Cr2 (cooling ramp 2)
Cr1 (cooling ramp 1)
AO1 Ramp
OFF
= select / set value
AO1 Minimum Voltage
0.0 Vdc
Go to "AO2"
AO1 Maximum Voltage
10.0 Vdc
Go to "AO2"
StFl (stpnt airflow 0-10 Vdc)*
AO2 DIR-REV
DIR (dir ec t )
REV (reverse)
CO2 (carbon dioxide)
Hr2 (heating ramp 2)
Hr1 (heating ramp 1)
Cr2 (cooling ramp 2)
Cr1 (cooling ramp 1)
AO2 Ramp
OFF
= select / set value
AO2 Minimum Voltage
0.0 Vdc
Go to "tmp "
AO2 Maximum Voltage
10.0 Vdc
Go to "tmp"
Main Menu Sub Menu Configuration
AO1
AO2
TO4
TO3
TO2
Output Config
TO1
= scroll menu items
= scroll menu items
MSV.20
MSV.22
AV.70 AV.71
AV.72 AV.73
BV.25
BV.26
* = StFl not available on
pressure dependent model
EVCB14NDT4S
On (fan continuously on )
Auto (fan follows demand )
AO1
= Auto and On options are for
fan powered box applications
and are only available with
models :
- EVCB14NIT4S
- EVCB14NDT4S
- EVCB14NIT4SF
On (fan continuously on )
Auto (fan follows demand )
AO2
OPt (Options)
Only available with CO
2
sensor models
Main Menu
APPS (Applications )
PrSs (Pressure )
rMp (Ramps)
NET (Network)
HrS (Time & Date)
Setc (Settings )
Mot (Motor )
tMp (Temperature )
OutP (Outputs)
InPt (Inputs )
*** To save any changes , press on TRL and on TDU ***
*** To the previous step without saving, press on TRL and TDU ***