Networkable VAV Controller
Specification and Installation Instructions
www.neptronic.com EVCB Standard Page | 11
Analog Outputs – Menu (4 of 6) | AO1 and AO2
StFl (stpnt airflow 0-10 Vdc)*
AO1 DIR- REV
DIR (dir ec t )
REV (reverse)
CO2 (carbon dioxide)
Hr2 (heating ramp 2)
Hr1 (heating ramp 1)
Cr2 (cooling ramp 2)
Cr1 (cooling ramp 1)
AO1 Ramp
OFF
= select / set value
AO1 Minimum Voltage
0.0 Vdc
Go to "AO2"
AO1 Maximum Voltage
10.0 Vdc
Go to "AO2"
StFl (stpnt airflow 0-10 Vdc)*
AO2 DIR-REV
DIR (dir ec t )
REV (reverse)
CO2 (carbon dioxide)
Hr2 (heating ramp 2)
Hr1 (heating ramp 1)
Cr2 (cooling ramp 2)
Cr1 (cooling ramp 1)
AO2 Ramp
OFF
= select / set value
AO2 Minimum Voltage
0.0 Vdc
Go to "tmp "
AO2 Maximum Voltage
10.0 Vdc
Go to "tmp"
Main Menu Sub Menu Configuration
AO1
AO2
TO4
TO3
TO2
Output Config
TO1
= scroll menu items
= scroll menu items
MSV.20
MSV.22
AV.70 AV.71
AV.72 AV.73
BV.25
BV.26
* = StFl not available on
pressure dependent model
EVCB14NDT4S
On (fan continuously on )
Auto (fan follows demand )
AO1
= Auto and On options are for
fan powered box applications
and are only available with
models :
- EVCB14NIT4S
- EVCB14NDT4S
- EVCB14NIT4SF
On (fan continuously on )
Auto (fan follows demand )
AO2
OPt (Options)
Only available with CO
2
sensor models
Main Menu
APPS (Applications )
PrSs (Pressure )
rMp (Ramps)
NET (Network)
HrS (Time & Date)
Setc (Settings )
Mot (Motor )
tMp (Temperature )
OutP (Outputs)
InPt (Inputs )
*** To save any changes , press on TRL and on TDU ***
*** To the previous step without saving, press on TRL and TDU ***