Networkable VAV Controller
Specification and Installation Instructions
www.neptronic.com EVCB Standard Page | 9
Inputs – Menu (2 of 6) | AI1, AI2, DI1 and DI2
DI2
mor (Motor position)
mor (Motor position )
ASt (Air s upply temp sensor )
CO2 (carbon dioxide)
StFl*(setpnt airflow 0-10Vdc)
AI 1 Signal Type
EtS (external temp sensor )
OFF (disabled)
DI1
AI2
Config Input
AI1
NoHt (normally heat )
NoCl (normally cool )
SENs (sensor) CH Over Setpnt
24°C
= s croll menu items
= select / set value
= select / set value
nSbc (night set back closed)
nSbo (night set back open)
OCCc (occupancy closed)
OCCo (occupancy open)
NSB-OCC Contact
OFF
Go to "DI2"
NSB Overide delay Min
120 min (0-180 )
No OCC Overide Delay Min
120 min (0 -180 )
Off
NSB Mode
StP (setpoint)
No OCC Heating setpnt
16°C / 61°F
No OCC Cooling setpnt
28°C / 82°F
Go to "DI2"
NSB Heating setpnt
16°C / 61°F
NSB Cooling setpnt
28°C / 82°F
Go to
"OutP"
DI 2 Signal Type
NC (normally closed )
OVH2 (override heat 2 )
OVH1 (override heat 1 )
Ovrd (override all)
NoCl (normally cool )
OFF
NoHt (normally heat )
OVHt (override all heat )
= select / set value
DI2 Delay Seconds
120 (0-3600)
DI2 Contact
NO (normally open )
Go to "OutP"
Go to "OutP"
AI1
DI1
DI2
Main Menu Sub Menu Configuration
= scroll menu items
CO2 Maximum Range
2000 ppm
CO2 Setpnt
800 ppm
Go to "AI2"
Go to "AI2"
Go to "AI2"
ASt (Air s upply temp sensor )
CO2 (carbon dioxide)
StFl*(setpnt airflow 0-10Vdc)
AI 2 Signal Type
EtS (external temp sensor )
OFF (disabled)
NoHt (normally heat )
NoCl (normally cool )
SENs (sensor) CH Over Setpnt
24°C
= select / set value
AI2
CO2 Maximum Range
2000 ppm
CO2 Setpnt
800 ppm
Go to "DI1 "
Go to "DI1 "
Go to "DI1 "
OPEn
NSB Motor Mode
Auto
Go to "DI1"
Go to "OutP"
MSV.1
AV. 58
AV.140 AV.141
AV.58
AV.140
AV.61
AV.60
MSV.2
MSV.10
MSV.14
AV.141
AV.19
BV.20
AV.18
AV.19 AV.18
MSV.36
AV.64
BV.36
* = StFl not available on
pressure dependent model
EVCB14NDT4S
Go to "AI2"
YES
CO2 DISPLAY
NO
BV.65
OPt (Options)
Only available with CO
2
sensor models
Main Menu
APPS (Applications )
PrSs (Pressure )
rMp (Ramps)
NET (Network)
HrS (Time & Date)
Setc (Settings)
Mot (Motor)
tMp (Temperature )
OutP (Outputs)
InPt (Inputs )
To display CO
2
without generating
an alarm, use a setpoint higher than
2000ppm or the CO
2
Maximum
Range (highest of the 2).
When set to YES , the unit will not display
the time when in Operation Mode
Go to "DI1"
YES
CO2 DISPLAY
NO
BV.65
When set to YES , the unit will not display
the time when in Operation Mode
To display CO
2
without generating
an alarm, use a setpoint higher than
2000ppm or the CO
2
Maximum
Range (highest of the 2).
Appears only if using thermostats
with temperature and humidity
sensors.
For TRLG, TRLGH and TDU
thermostats with CO
2
sensors, go to
OptҸmenu.
Go to "AI2"
*** To save any changes , press on TRL and on TDU ***
*** To the previous step without saving, press on TRL and TDU ***
Appears only if using thermostats
with temperature and humidity
sensors.
For TRLG, TRLGH and TDU
thermostats with CO
2
sensors, go to
OptҸmenu.