Step 8: Return the failed part to NetApp
After you replace the part, you can return the failed part to NetApp, as described in the
RMA instructions shipped with the kit. Contact technical support at
NetApp Support, 888-
463-8277 (North America), 00-800-44-638277 (Europe), or +800-800-80-800
(Asia/Pacific) if you need the RMA number or additional help with the replacement
procedure.
Hot-swap a fan module - FAS8300 and FAS8700
To swap out a fan module without interrupting service, you must perform a specific
sequence of tasks.
You must replace the fan module within two minutes of removing it from the chassis. System
airflow is disrupted and the controller module or modules shut down after two minutes to avoid
overheating.
You can use the following animation, illustration, or the written steps to hot-swap a fan module.
Replacing a fan
Steps
1394