BEFORE INSTALLATION: READ THIS MANUAL
SAVE THESE INSTRUCTIONS
Installing contractor and homeowner should read and be informed as to the proper installation and operation of this boiler.
The manufacturer will not be responsible for improper installation or operation. This manual and all associated instruction
material should be conspicuously posted near the boiler.
INSTALLATION, OPERATING
AND
SERVICE INSTRUCTIONS
CG-D™ SERIES
GAS BOILER
Price - $3.00
9700609
For service or repairs to boiler, call your heating contractor. When seeking information on boiler,
provide Boiler Model Number and Serial Number as shown on Rating Label.
Boiler Model Number
CG D
Boiler Serial Number Installation Date
Heating Contractor Phone Number
Address

Questions and Answers

  • R
    Robert MillerAug 20, 2025
    What to do if the New Yorker CG20D Boiler main flame does not light?
    • A
      Ashley SullivanAug 20, 2025
      If the main flame does not light, check the orifice size for any blockage. Also, verify if there's 24 volts across control terminals P5-8 and P5-5. If there is no voltage, the control might be defective.
  • P
    Patricia BaileyAug 22, 2025
    Why is my New Yorker CG20D circulator on but the boiler is off?
    • S
      smillerAug 22, 2025
      If the boiler is off but the circulator is on, check the boiler temperature. If the boiler water temperature is higher than the start temperature (default 140 F) and the circulator pre-purge time (default 2 minutes) has not expired, the boiler start will be delayed until the water temperature drops or the time expires.
  • S
    Susan PhillipsAug 25, 2025
    What to do if my New Yorker Boiler temperature sensor fails?
    • A
      Albert WaltersAug 25, 2025
      If the temperature sensor fails, check that the sensor is securely attached to the control P7 connector and that the sensor wire is not damaged. If the problem continues, replace the sensor. If the problem still persists, replace the control.
  • S
    Sherri HendersonAug 26, 2025
    What to do if the New Yorker Boiler damper failed to open?
    • E
      Emily TaylorAug 26, 2025
      If the damper failed to open, check for a loose connection between the control and vent damper, and inspect the damper harness. Also, check for any obstruction in the path of the damper. If the error does not clear, replace the control.
  • R
    Ryan KingAug 27, 2025
    How to fix a New Yorker Boiler with a flame rod shorted to ground?
    • E
      ericjohnsonAug 27, 2025
      To fix a flame rod shorted to ground, check for excessive condensate, dry the pilot, and adjust the setpoint higher. Also, check for a loose or damaged ignition wire.
  • K
    Katherine NewmanAug 29, 2025
    What to do if the New Yorker CG20D spark does not stop when pilot lights?
    • S
      Stacey WatsonAug 29, 2025
      If the spark does not stop when the pilot lights, check for a loose connection in the ignition cable or ground wire. You should also check the continuity of the ignition cable.
  • D
    denise74Aug 31, 2025
    What to do if New Yorker CG20D Boiler has flame present out of sequence?
    • K
      karenpenaAug 31, 2025
      If there is flame present out of sequence, check the gas valve for proper operation.
  • V
    Virginia MitchellSep 2, 2025
    What to do if New Yorker Boiler is waiting for limit to open?
    • E
      escobarcarolSep 2, 2025
      If the boiler is waiting for a limit to open, check the blocked vent switch and the flame rollout switch.
  • I
    icarterSep 4, 2025
    What to do if the New Yorker Boiler damper failed to open (STA 20)?
    • J
      Jessica WallSep 4, 2025
      If the damper failed to open (STA 20), check if the control terminal 'P6 - 5' (yellow wire) is energized during status 'STA18' or 'STA 20'. Also, check for any obstruction in the path of the damper.
  • K
    kennethmarshSep 6, 2025
    What to do if my New Yorker CG20D thermostat input is higher than threshold?
    • M
      Michael Marquez PhDSep 6, 2025
      If the thermostat input is higher than the threshold, check the thermostat wiring.