MASTERTRACE Appendix G MR100 for Windows CE
G.8
Once the desired heater is selected, MR100 will be constantly polling the heater to populate the
alarm setpoint & measured values data boxes with its latest data obtained through communication. Also the
bar graphs will be plotted in blue & red colors, and proportionally according to their respective variables’
measured values.
10. Module Commissioning/Addressing Function Page
Module Commissioning/Addressing Function Page, as shown in Figure G.8, can be opened by
a click on the Module Commission tap.
Figure G.8 – Module Commissioning/Addressing Function Page
Module Commissioning/Addressing includes three operations. They are:
(1) Reset Control Module - It is designed to reset the setpoints of all heaters on a control module
to their default values.
(2) Read Module Number - It is designed to read the module number of a control module.
(3) Set Module Number - It is designed to set the module number of a control module.
Each operation can be carried out if the following 2 conditions are met:
(1) MR100’s Program Enable is Enabled.
(2) The target control module is the only module in listening new address mode within the
network. This can be realized by setting the target control module’s ADRESS dip switch to Enable
position, and cycle the power of the target control module.
Module Commissioning/Addressing Page consists of 2 edit boxes and 1 button, i.e., Option
drop-down edit box, Module Number drop-down edit box and Start command button.