A.6
MASTER
TRACE
Appendix A
Display Message
Details - Setpoints
MESSAGE NO: S1-23 APPLIES TO: Selected Heater
DEFAULT VALUE: 0.5 min VALUE RANGE: 0.5 to 15 min
DISPLAY MODE: Advanced RESTRICTIONS: none
This functions sets the heater on time period (in minute) when tracecheck is
activated.
MESSAGE NO: S1-24 APPLIES TO: Selected Heater
DEFAULT VALUE: 120V VALUE RANGE: 100 to 600 V, (measured)
DISPLAY MODE: Advanced RESTRICTIONS: none
This functions sets the Heater Voltage. For 1-point and 2-point Control Modules
with circuits at 300 V or less, set to “measured”. Otherwise, set to the heater
supply voltage. This value is used to compute Energy Used and Energy Cost.
MESSAGE NO: S1-25 APPLIES TO: Selected Heater
DEFAULT VALUE:off VALUE RANGE: 0 to 300 V, off
DISPLAY MODE: Advanced RESTRICTIONS: Single Phase, 1 and 2 point
modules
This function sets the Low Voltage Alarm setpoint. To disable this alarm set the
value to “off”. When the Heater Voltage is less than or equal to this setpoint, the
Low Voltage Alarm is activated and a “LOW VOLTAGE ALARM” message is
added to the System Status messages. The alarm deactivates when the Heater
Voltage rises above this alarm setpoint.
Setpoints: Heater Setup Menu
MESSAGE NO: S2-01 APPLIES TO: Interface Module
DEFAULT VALUE: N/A VALUE RANGE: N/A
DISPLAY MODE: Advanced RESTRICTIONS: None
This message displays the name of the sub-menu when entered.
MESSAGE NO: S2-02 APPLIES TO: Interface Module
DEFAULT VALUE:Selected Htr VALUE RANGE: Set by MODULE RANGE
function
DISPLAY MODE: Advanced RESTRICTIONS: None
This function selects the heater circuit. Each heater circuit has a unique two-part
Heater Number. The first part is the Module Number and the second part is the
heater circuit within the Control Module. Press [VALUE ñ] or [VALUE ò] and
then press [STORE] to select a heater circuit. For convenience and to reduce
human error, the Heater Name is also displayed.
HEATER VOLTAGE:
120 V ?
LOW VOLTAGE
ALARM: 100 V ?
SETPOINTS:
HEATER SETUP
SELECT HT: 1-1?
NONAME &
TRACECHECK HTR ON
TIME: 0.5 min ?