MASTER
TRACE
3.19
Chapter 3
Product Description
3.4 Model Codes for Control Panels
MasterTrace™ systems are available in different configurations depending on the application. The product model code
on the MasterTrace™ system identifies the features.
For mixed module panel, add controller model suffix as required.
eg. MS-10DXH2-5TXH2R-E1D3-RTD-SP
Assumed: 1 MS-10ADXH0 MODULE
1 MS-5ATXH0 MODULE
MS - 10 DXH 2 R - E1D1 - RTD
Number of Points
Enclosure Options
E1: NEMA-4 Steel
E2: NEMA-4X FRP
E3: NEMA-4X Stainless Steel
E4: NEMA-4X Aluminum
D1: Local Interface
D2: Local Interface w/ Shroud
D3: Group Interface
D4: Group Interface w/ Shroud
F1: Floor Stand (not available for all models)
D5: VFD Local Interface
D6: VFD Local Interface w/ Shroud
D7: VFD Group Interface
D8: VFD Group Interface w/ Shroud
D9: Touch Screen Group Interface
Switch Type
1-Pole, External Solid State: SXH
2-Pole, Internal Mechanical: DIN
2-Pole, External Solid State: DXH
3-Pole, External Solid State: TXH
Switch Rating
No Switches: 0
30A/240Vac: 2
50A/240Vac: 3
100A/240Vac: 4
30A/600Vac: 5
50A/600Vac: 6
100A/600Vac: 7
Additional Options
A1: Green LED Alarm Indicator
A2: Red LED Alarm Indicator
Bx: Distribution Panel with x Amp Main
RTD: 7ft RTD Sensor
SP: Special Modification
X1: Control Transformer 208VAC Input
X2: Control Transformer 240VAC Input
X3: Control Transformer 277VAC Input
X4: Control Transformer 480VAC Input
X5: Control Transformer 600VAC 2P/
347VAC 1P Input
XP: Non-Classified to Class I, Division 1
YP: Class I, Division 2 to Division 1
ZP: Non-Classified to Class I, Division 2
ETH: Ethernet Modbus TCP to RS485
Modbus RTU Gateway on Serial
Port 2
RTD
Single RTD per heater: blank
Dual RTD per Heater: R
One RTD per module: O
No RTD: N
Single thermocouple per heater: T
Single RTD Transmitter
connection per heater: X
Single RTD per heater via RTD
Sampler with Modems: S10M
Dual RTD per heater via RTD
Sampler with Modems: S20M
Single RTD per heater via RTD
Sampler with RS485: S10R
Dual RTD per heater via RTD
Sampler with RS485: S20R