Chapter 5
Operation
5.5 Setpoint Values Menu: Three-Phase Modules (1- and 5-point only)
SETPOINTS:
OPERATING VALUES
[MESSAGEô ]
SELECT HT:1-1?
NONAME &
[MESSAGEô ]
HEATER ENABLED?
yes
?
[MESSAGEô ]
HEATER SETPOINT:
5°C
?
[MESSAGEô ]
LOW TEMPERATURE
ALARM: 2°C
?
[MESSAGEô ]
HIGH TEMPERATURE
ALARM: off
?
[MESSAGEô ]
A: LOW CURRENT
ALARM: off
?
[MESSAGEô ]
C: HIGH CURRENT
ALARM: off
?
[MESSAGEô ]
[SETPOINT]
ò
1
[SETPOINT]
ò
SETPOINTS:
HEATER SETUP
[MESSAGEô ]
SELECT HT: 1-1?
NONAME &
[MESSAGEô ]
HTR 1-1 NAME:
NONAME
?
[MESSAGEô ]
MASTER OVERRIDE:
off
?
[MESSAGEô ]
PROPORTIONAL
CONTROL: off
?
[MESSAGEô ]
DEADBAND
2 C°
?
[MESSAGEô ]
IF RTD FAILS
HEATER GOES: off
?
[MESSAGEô ]
RTD MODE:
2 RTDs, lowest
?
[MESSAGEô ]
[SETPOINT]
3
4
ò
DISPLAY MODE:
normal user
?
[MESSAGEô ]
DEFAULT DISPLAY:
system status
?
[MESSAGEô ]
DISPLAY TIMEOUT:
60 seconds
?
[MESSAGEô ]
SCAN TIME:
3 seconds
?
[MESSAGEô ]
TEMPERATURE
UNITS: celcius
?
[MESSAGEô ]
COST PER kWh:
$0.05
?
[MESSAGEô ]
STAGGER START:
off
?
[MESSAGEô ]
NUM OF AMB SENSE
HTRS: 0
?
[MESSAGEô ]
SETPOINTS:
SYSTEM SETUP
[MESSAGEô ]
MODULE RANGE:
1-30
?
[MESSAGEô ]
MODULE LIST:
MOD: 1? SEL:yes?
[MESSAGEô ]
[SETPOINT]
ò
6
MANUAL SYSTEM:
ALARM: disabled
?
[MESSAGEô ]
GF TEST:
test now
?
[MESSAGEô ]
go to 1
SETPOINTS:
SETPOINTS TEST
[MESSAGEô ]
MANUAL ALARM:
disabled
?
[MESSAGEô ]
MANUAL HEATER:
disabled ?
[MESSAGEô ]
RESET CONTROL
MODULE? no
?
[MESSAGEô ]
RESET MR100:
no
?
[MESSAGEô ]
MANUAL VERSION:
1501-0006_1
[MESSAGEô ]
FOR ASSISTANCE:
(403) 735-9555
[MESSAGEô ]
go to 6
5
Restrictions
1 5- & 10-point Modules
2 MR100 Interface Module
Advanced User Mode
2
2
2
2
2
READ MODULE
NUMBER: 1
?
[MESSAGEô ]
ALARM CONTACTS:
MECH: NC
?
SS: NC
?
[MESSAGEô ]
2
2
ððð
GROUND FAULT
TRIP: 30mA
?
[MESSAGEô ]
TRACECHECK HTR ON
TIME: 0.5 MIN
?
[MESSAGEô ]
HEATER VOLTAGE:
120V
?
[MESSAGEô ]
go to 3
2
B: HIGH CURRENT
TRIP: off
?
[MESSAGEô ]
B: HIGH CURRENT
ALARM: off
?
[MESSAGEô ]
A: HIGH CURRENT
ALARM: off
?
[MESSAGEô ]
C: LOW CURRENT
ALARM: off
?
[MESSAGEô ]
B: LOW CURRENT
ALARM: off
?
[MESSAGEô ]
COPY TO OTHER
HEATERS: no
?
[MESSAGEô ]
go to 4
1
FIRMWARE VERSION:
D1-02-01
[MESSAGEô ]
SET MODULE
NUMBER: no
?
[MESSAGEô ]
BAUD RATE 1:
1200
?
[MESSAGEô ]
go to 5
MR100 BAUD RATE:
1200
?
[MESSAGEô ]
RTD BOARD:
On Board
?
[MESSAGEô ]
A: HIGH CURRENT
TRIP: off
?
[MESSAGEô ]
TRACECHECK CYCLE
TIME: off
?
[MESSAGEô ]
GROUND FAULT
ALARM: 20mA
?
[MESSAGEô ]
POWER LIMIT
CURRENT: off
?
[MESSAGEô ]
1
C: HIGH CURRENT
TRIP: off
?
[MESSAGEô ]
go to 2
1
ALARM LIGHT MODE:
alarm off
?
[MESSAGEô ]
AMBIENT SENSING
HEATER: None
?
[MESSAGEô ]
2
1
BAUD RATE 2:
1200
?
[MESSAGEô ]
AMBIENT RTD
TEMP: 5°C
&
[MESSAGEô ]
2