EasyManua.ls Logo

Nextron MASTERTRACE - Page 30

Nextron MASTERTRACE
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MASTER
TRACE
3.17
Chapter 3
Product Description
3.3.15 ML100 Dedicated Interface Module
Control Power
Power Requirements: From Control Module ML100 Interface
connector: +5Vdc/0.1A, +8Vdc/0.4A,
-6.5Vdc/1mA
Communications
Port: 1 Dedicated parallel connection
Interconnect: 26-pin IDC ribbon cable
Cable Length: 3 feet maximum
Environment
Approval: CSA NRTL/C
Class 1, Div.II, Groups A,B,C,D
Class 1, Zone-2, Groups IIC
Operating Range: -40°C to +60°C
(LCD Display: -20°C to +60°C)
(VFD Display: -40°C to +60°C)
Conformal Coating: Boards conformal coated for hostile
environments
User Interface
Display: 16-character x 2-line LCD or VFD
Alpha-numeric display
Keypad: 9 tactile keys, polyester faceplate
- Setpoint, measured, status
- Message Up, Message Down
- Value Up, Value Down
- Reset
- Store
Contrast: Adjustable by potentiometer
Panel Indicators: Power on
Current heater display on
Serial communication active
System alarm
Process alarm
Bezel
Material: 304 Stainless steel
Mounting: For mounting on NEMA-12 or NEMA-4
enclosure door. Includes gasketing.
Optional: 304 Stainless steel shroud with plexi-
glass hinged cover to protect keypad
from physical damage.
Specifications subject to change without notice.
3.3.16 MR100 Group Interface Module
Control Power
Power Requirements: 12VA @ 120Vac, 50 or 60Hz
Communications
Ports: 1 Serial network connections
Type: RS485
Protocol: Modbus® RTU.
Transmission Rate: 600, 1200, 2400, 4800, 9600 baud.
Interconnect: 2-wire, shielded, twisted pair.
Highway Distance: 4,000 feet without repeater.
Modules per Highway: (1) MR100 and (30) Control Modules.
Environment
Approval: CSA NRTL/C
Class1, Div.II, Groups A,B,C,D
Class1 Zone 2, Group IIC
Operating Range: -40°C to +60°C
(LCD Display: -20°C to +60°C)
(VFD Display: -40°C to +60°C)
Conformal Coating: Boards conformal coated for hostile
environments
Alarm
Alarm Output: Programmable for NO or NC contacts
One DC opto-isolated contact
One dry mechanical contact
Alarm Output Rating:
Hazardous Areas: DC contact: 30Vdc/0.1A, 500mW max
Dry mech contact: 30Vdc/10mA max
250Vac/0.5A max
(not subject to a corrosive environment)
Ordinary Areas: DC contact: 30Vdc/0.1A, 500mW max
Dry mech contact: 120Vac/1.0A max
30Vdc/0.1A max
Alarm Light Output: LED Indicator: 12Vdc/30mA
Alarm Messages: Refer to Control Module Specifications
User Interface
Display: 16-character x 2-line LCD or VFD
Alpha-numeric display
Keypad: 9 tactile keys, polyester faceplate
- Setpoint, measured, status
- Message Up, Message Down
- Value Up, Value Down
- Reset
- Store
Contrast: Adjustable by potentiometer
Panel Indicators: Power on
Current heater display on
Serial communication active
System alarm
Process alarm
Bezel
Material: 304 Stainless steel
Mounting: For mounting on NEMA-4/4X
enclosure door. Includes gasketing.
Optional: 304 Stainless steel shroud with plexi-
glass hinged cover to protect keypad
from physical damage.

Table of Contents