EasyManua.ls Logo

Nextron MASTERTRACE - Page 35

Nextron MASTERTRACE
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MASTERTRACE
4.3
Chapter 4 Installation
4.9.1 Enter Program Changes: Refer to the Programming
Sheet for Control Panel & Modules in the panel drawing if
it is available. If not, Refer to Figure 4.2 for Sample
Programming Worksheet. Ignoring the alarm messages
and lights, enter all required user setup changes. The
Program Enable edit box in MR100 for Windows CE or
Program Enable dip switch on the MR100/ML100 Inter-
face Module must be set to ENABLE to allow program-
ming. Refer to Figure 2 in Appendix G, or Figure 5.9 for
ML100 Dedicated Interface Module, or Figure 5.10 for
MR100 Group Interface Module. It is recommended that
this Program Enable edit box or dip switch be set to
DISABLE to prevent unauthorized entry of program
changes.
4.9.2 Turn On Heater Power: Close the circuit breakers
for all heat trace circuits controlled by the MasterTrace
control panel.
4.9.3 Respond to Alarm Conditions: Examine each alarm
condition and correct problems as required. High Current
and Low Temperature alarms should be ignored during
start-up and until normal operating levels have been
reached. Refer to Appendix C: Summary of Alarms and
Causes for information on potential causes of alarms.
4.9.4 Check Actual Readings: Once the system has
reached normal operating temperatures, check the
individual temperature, current and ground fault current
readings against expected values for each circuit. This can
indicate wiring or design errors.
4.9.5 Check the RTD Wiring: Locate and open the
junction box or head of the selected RTD. Either
disconnect the RTD or short the wires. The RTD Short or
RTD Open alarm will be displayed on the Interface
Module showing the Heater Name. Confirm that the
displayed heater matches the heater of the selected RTD.
Warning - Explosion Hazard - Substitution
of components may impair suitablility for
Class 1, Division 2 or Class 1, Zone 2.
Warning - Explosion Hazard - Do not
disconnect equipment unless power has
been switched off or the area is known to be
non-hazardous.
Warning - The ground fault trip function is
intended for equipment protection only and
should not be used in place of ground fault
protection for personnel protection where
this is required.
There are no consumable components contained in any of
the models covered in this manual.
There is no cleaning requirements for any of the models
covered in this manual.
Caution - Equipments are not evaluated for use
in a corrosive atmosphere.

Table of Contents