MESSAGE NO: S3-03 APPLIES TO: Interface Module
DEFAULT VALUE: 1-30 VALUE RANGE: 1-30, 31-60, … , 211-240,
241-254
DISPLAY MODE: Advanced RESTRICTIONS: MR100 Interface
This function selects the range of Control Module numbers connected to this
Interface Module. All Control Modules connected to this Interface Module must
be within this range.
MESSAGE NO: S3-04 APPLIES TO: Interface Module
DEFAULT VALUE: advanced user VALUE RANGE: advanced user, normal user
DISPLAY MODE: All RESTRICTIONS: None
This function determines what messages are displayed. If set to “advanced user”,
all messages are displayed. If set to “normal user”, only the basic messages are
displayed. Each message listed in this appendix shows the Display Mode required
to see the message. “Advanced” indicates that the display mode must be set to
“advanced user” to view the message.
MESSAGE NO: S3-05 APPLIES TO: Interface Module
DEFAULT VALUE: System status VALUE RANGE: See values below
DISPLAY MODE: Advanced RESTRICTIONS: None
This function specifies the information that will be displayed when no key has
been pressed for the Display Timeout interval as described below.
VALUE INFORMATION DISPLAYED
System status Alarm status of all the heaters
Heater status Heater status of selected heater
Heater temp Temperature of the selected heater
Scan heater All measured values of the selected heater
Scan temps Temperatures of all enabled heaters
Scan currents Phase currents of all enabled heaters
Scan gnd faults Ground fault currents of all enabled heaters
Scan all heaters All measured values of all enabled heaters
MESSAGE NO: S3-06 APPLIES TO: Interface Module
DEFAULT VALUE: 60 seconds VALUE RANGE: 5 to 600 s, off
DISPLAY MODE: Advanced RESTRICTIONS: None
This function sets the length of time, from the last key press, to automatically
return to the Default Display information. To disables this function set the value to
“off”.
MESSAGE NO: S3-07 APPLIES TO: Interface Module
DEFAULT VALUE: 3 seconds VALUE RANGE: 1 to 10 seconds
DISPLAY MODE: Advanced RESTRICTIONS: None
This function sets the length of time between the display of successive messages.
Select a value that is comfortable for the reading speed of the operator.
MESSAGE NO: S3-08 APPLIES TO: Interface Module
DEFAULT VALUE: Celsius VALUE RANGE: Celsius, Fahrenheit
DISPLAY MODE: Advanced RESTRICTIONS: None
This function sets the units of measure for temperature. All temperatures are
displayed in the selected units of either Celsius degrees (C°) or Fahrenheit
degrees (F°).
MODULE RANGE
1-30 ?
DISPLAY MODE:
advanced user ?
DEFAULT DISPLAY:
System Status ?
DISPLAY TIMEOUT:
60 seconds ?
SCAN TIME:
2 seconds ?
TEMPERATURE UNITS:
Celcius ?