B.2
Appendix B
Display Message
Details - Measured
MESSAGE NO: M1-06 APPLIES TO: Selected Heater
DEFAULT VALUE: N/A VALUE RANGE: -50 to 500 °C
-58 to 932 °F
DISPLAY MODE: All RESTRICTIONS: Dual RTD Modules
The displayed value is the actual measured temperature of RTD-B sensor for this
heater circuit. It is used to calculate the Heater Control Temperature based on the
RTD MODE function. If the temperature is outside the value range then “RTD
OPEN” or “RTD SHORT” is displayed.
MESSAGE NO: M1-07 APPLIES TO: Selected Heater
DEFAULT VALUE: N/A VALUE RANGE: 0 to 100%
DISPLAY MODE: Advanced RESTRICTIONS: None
The displayed value is the percentage duty cycle of the heater circuit. For example,
a percentage duty cycle of 30% means that the circuit is energised for 3 out of 10
supply cycles.
MESSAGE NO: M1-08 APPLIES TO: Selected Heater
DEFAULT VALUE: N/A VALUE RANGE: 0 to 100.0 A
DISPLAY MODE: All RESTRICTIONS: Single-Phase Modules
The displayed value is the actual single-phase current of the heater circuit. If the
heater is off, this value will be zero. The maximum value range for internal
switching modules is 30.0 A. If the current exceeds the value range then “O.L.” is
displayed. The use of PROPORTIONAL CONTROL or POWER LIMIT functions
can reduce the phase current by reducing the circuit voltage.
MESSAGE NO: M1-09 APPLIES TO: Selected Heater
DEFAULT VALUE: N/A VALUE RANGE: 0 to 100.0 A
DISPLAY MODE: All RESTRICTIONS: Three-Phase Modules
The displayed value is the actual phase-A current of the heater circuit. If the heater
is off, this value will be zero. If the current exceeds the value range then “O.L.” is
displayed. The use of PROPORTIONAL CONTROL or POWER LIMIT functions
can reduce the phase current by reducing the circuit voltage.
MESSAGE NO: M1-10 APPLIES TO: Selected Heater
DEFAULT VALUE: N/A VALUE RANGE: 0 to 100.0 A
DISPLAY MODE: All RESTRICTIONS: Three-Phase Modules
The displayed value is the actual phase-B current of the heater circuit. If the heater
is off, this value will be zero. If the current exceeds the value range then “O.L.” is
displayed. The use of PROPORTIONAL CONTROL or POWER LIMIT functions
can reduce the phase current by reducing the circuit voltage.
MESSAGE NO: M1-11 APPLIES TO: Selected Heater
DEFAULT VALUE: N/A VALUE RANGE: 0 to 100.0 A
DISPLAY MODE: All RESTRICTIONS: Three-Phase Modules
The displayed value is the actual phase-C current of the heater circuit. If the heater
is off, this value will be zero. If the current exceeds the value range then “O.L.” is
displayed. The use of PROPORTIONAL CONTROL or POWER LIMIT functions
can reduce the phase current by reducing the circuit voltage.
RTD-B ACTUAL
TEMP: 6°C &
HEATER AT 100% &
POWER
HEATER CURRENT
4.6A &
A:HEATER CURRENT
4.6A &
B:HEATER CURRENT
4.6A &
C:HEATER CURRENT
4.6A &