13.
Pipe outlet on rear right-hand side:
Insert the pipes and condensation drain pipe
through the hole in the wall. Suspend the unit on
the previously installed wall mounting.
NOTE
Insulate the hole in the wall to prevent the
sensors being affected by the outdoor air.
14.
Pipe outlet on rear left-hand side:
Insert the pipes from outside, then bend them to
the right.
Caution
Adapt the length of the pipes so that they
fit the pipe connections on the indoor unit.
15.
Press lightly to hook the unit to the wall mounting.
16.
Connect the cables to the terminal block. Secure
the cable using the cable tie. Also see section
"Electrical connection" on page 6.
WARNING!
Ensure that all connections are tightened
properly on the terminal block. Non-
tightened terminals lead to overheating,
problems with the heat pump's function
and are a fire risk.
17.
Lead out the condensation hose and ensure the
correct fall. Make a water seal if necessary.
Pump down
See the outdoor unit's installation manual for detailed
information regarding "Pump down".
Pump down means retrieving all refrigerant in the
outdoor unit without losing the system's filling. This is
required when the climate unit is to be removed or
during repair of the cooling circuit.
AG-WT10Chapter 5 | Installation10