General
INSTALLATION REQUIREMENTS
AMS 10-16AMS 10-12AMS 10-8AMS 10-6
0.25 MPa (2.5 Bar)Max pressure, climate system
55/45 °CHighest recommended supply/return temperature at dimen-
sioned outdoor temperature
+65 °CMax temperature in AMS 10
+58 °CMax flow line temperature with compressor
+7 °CMin supply temperature cooling
+25 °CMax supply temp. cooling
30 mMax. pipe length, refrigerant pipe *
80 l80 l50 l20 lMin. volume, climate system during heating, cooling**
100 l100 l80 l50 lMin. volume, climate system during underfloor cooling**
0.57 l/s0.57 l/s0.38 l/s0.29 l/sMax flow, climate system
0.29 l/s0.29 l/s0.19 l/s0.19 l/sMin flow, climate system, 100 % circulation pump speed (de-
frosting flow)
0.15 l/s0.15 l/s0.12 l/s0.09 l/sMin flow, heating system
0.20 l/s0.20 l/s0.16 l/s0.11 l/sMin flow, cooling system
*AMS 10-6: If the length of the refrigerant pipes exceeds 15 metres, extra refrigerant must be added at a rate of 0.02 kg/m.
AMS 10-8/12/16: If the length of the refrigerant pipes exceeds 15 metres, extra refrigerant must be added at a rate of 0.06 kg/m.
** Refers to circulating volume.
External circulation pump must be used when the pressure drop in the system is greater than the available external pressure. In such cases,
a bypass line with a non-return valve must also be installed.
A bypass valve must be used if min. system flow cannot be guaranteed.
15Chapter 3 | System descriptionNIBE AMS10