Drain pan heater
AMS 10
AMS 10
PWB1-CNF EB11
PWB1-CNTH BT28 (tho-A)
CH
Thermostat
Open / ClosedTemperature
Open (off)35 °C ±5
Closed (on)25 °C ±5°
Drain pan heater
OffOnModel
3°C1°CAMS 10-8
5°C3°CAMS 10-12/-16
DRAIN PAN HEATER FOR AMS 10-6
The drain pan heater is on when the following conditions
are met:
• Operating mode is heating
• The temperature Tho-R is -2.0° C or lower
• The outdoor temperature Tho-A is -0° C or lower
• Tho-A minus Tho-R is greater than or equal to the value
A, which varies depending on the outdoor temperat-
ure. The value A is calculated using the table below:
Value ACurrent outdoor temperature
Tho-A
4.00°C
2.00° C to -5 °C
0.0-5° C to -10 °C
-5.0-10° C and lower
DRAIN PAN HEATER FOR AMS 10-8/-12/-16
The drain pan heater is on when the following conditions
are met:
• Operating mode is heating
• The compressor is running and 30 minutes have
passed since the compressor last stopped
• The outdoor temperature Tho-A (BT28) is -1° °C or
lower
Heating element
Power (W)Voltage (V)Model
110 W230 VAMS 10-6
100 W230 VAMS 10-8
120 W230 VAMS 10-12/-16
29Chapter 4 | Description of functionsNIBE AMS10