CONDITIONS DURING DEFROSTING
When the defrosting conditions are met, the outdoor
unit waits 40 seconds to confirm it. If the defrosting
conditions are changed during the 40 secs. Defrosting
will not start.
EEV-C opens fully and the compressor speed is set
to A rps.
B rpsA rps
5520Speed AMS 10-6
5025Speed AMS 10-8
5625Speed AMS 10-
12/-16
The 4-way valve switches after 5 seconds (AMS10-6),
1 second (AMS10-8) or 20 seconds (AMS10-12) after
the compressor speed reaches A rps or lower.
The fan is stopped when the fourway valve switches.
EEV-H is fully open and the compressor speed is fixed
for 1 minute to prevent low pressure.
The target speed for the compressor is then set to
B rps, the acceleration is 2 rps/10 seconds for AMS10-
12 if the low pressure is greater than 0.53 MPa (-7 °C).
For AMS10-8, the compressor speed is regulated
every five seconds to prevent the water temperature
or low pressure falling.
EEV-C regulates to 5 K in the event of overheating.
EEV-H regulates to 0.82 MPa at low pressure.
The fan is not active during defrosting. Other circum-
stances may make the fan rotate.
21Chapter 4 | Description of functionsNIBE AMS10