Sub-menus
Menu SERVICE has orange text and is intended for the
advanced user. This menu has several sub-menus.
Status information for the relevant menu can be found
on the display to the right of the menus.
operating settings Operating settings for the heat
pump.
system settings System settings for the heat pump,
activating accessories etc.
accessory settings Operational settings for different
accessories.
soft in/outputs Setting software controlled in and out-
puts on the input circuit board (AA3).
factory setting service Total reset of all settings (includ-
ing settings available to the user ) to default values.
forced control Forced control of the different compon-
ents in the heat pump.
start guide Manual start of the start guide which is run
the first time the heat pump is started.
quick start Quick starting the compressor.
NOTE
Incorrect settings in the service menus can
damage the heat pump.
MENU 5.1 - OPERATING SETTINGS
Operating settings can be made for the heat pump in
the sub menus.
MENU 5.1.1 - HOT WATER SETTINGS
start temp. economy / normal / lux
Setting range: 5 – 70 °C
Factory setting (°C):
luxurynormaleco-
nomy
kW
4744415Enamel
4643406
4542398
43403710
42393612
4845425Copper
4744416
4643408
44413810
43403712
4845425Stainless
4744416
4643408
44413810
43403712
stop temp. economy / normal / lux
Setting range: 5 – 70 °C
Factory setting (°C):
luxurynormaleco-
nomy
kW
5148455Enamel
5047446
4946438
47444110
46434012
5249465Copper
5148456
5047448
48454210
47444112
5249465Stainless
5148456
5047448
48454210
47444112
stop temp. per. increase
Setting range: 55 – 70 °C
Factory setting: 55 °C
Here you set the start and stop temperature of the hot
water for the different comfort options in menu 2.2 as
well as the stop temperature for periodic increase in
menu 2.9.1.
If several compressors are available set the difference
between engagement disengagement of them during
hot water charging and fixed condensing.
MENU 5.1.2 - MAX FLOW LINE
TEMPERATURE
climate system
Setting range: 20-80 °C
Default value: 60 °C
Set the maximum supply temperature for the climate
system here. If the installation has more than one cli-
mate system, individual maximum supply temperatures
can be set for each system. Climate systems 2 - 8 can-
not be set to a higher max supply temperature than cli-
mate system 1.
47Chapter 8 | Control - MenusNIBE F1245