5NIBE PB 10
Installation
General information for the installer
Checks
Check for a risk of condensation in the flue by reading off
the flue gas temperature 1 m down from the chimney top.
If the temperature drops below 80 °C during the winter,
there is a risk of condensation. If the flue gas temperature
only falls below 80 °C by a few degrees, it may be enough
to install a counter-draft hatch on the flue, between the
boiler and chimney, in the boiler room. If the flue gas
temperature drops below 75 °C, an insert pipe should be
installed the entire length of the chimney.
Adjustment with the instrument should also be carried if
the pellet size or quality is changed.
There must not be any overpressure in the fireplace at any
time, i.e. during ignition, operation or extinguishing.
This can be checked by unscrewing the sight glass and
checking that smoke does not enter the boiler room.
Control device
Starting:
Start the installation by setting the boiler's main switch to
1 or on. Increase boiler's double thermostat to the desired
boiler temperature.
Stopping:
Lower the boiler thermostat.
Emergency stop:
Set the main switch of the boiler to 0 or off.
Make adjustments to the burner using a
flue gas analysis instrument for optimal
combustion.