EasyManua.ls Logo

Nibe S1156 - Selectable Inputs and Outputs; Selectable Input Configuration; Selectable Output Functionality; myUplink Network Connection

Nibe S1156
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
If several accessories are to be connected, or are already
installed, the boards are connected in series.
Because there can be different connections for accessories
with accessory board (AA5), you should always read the in-
structions in the manual for the accessory that is to be in-
stalled.
+12V
GND
B
A
AA2-X30
4
3
2
1
AA5-X4
1
2
3
4
5
6
7
8
A
B
GND
A
B
GND
AA5-X4
1
2
3
4
5
6
7
8
A
B
GND
A
B
GND
Accessory 1
S1156
Accessory 2
Network cable for myUplink (W130)
In instances when you want to connect to myUplink using
a network cable instead of via wifi.
1. Connect the shielded network cable to the display.
2. Follow the flow meter’s cable out at the rear.
SELECTABLE OUTPUTS/INPUTS
S1156 has software-controlled AUX inputs and outputs for
connecting the external switch function (contact has to be
potential-free) or sensor.
In menu 7.4 - "Selectable in/outputs", you select the AUX
connection to which each function has been connected.
For certain functions, accessories may be required.
TIP
Some of the following functions can also be activ-
ated and scheduled via menu settings.
Selectable inputs
Selectable inputs on the base board (AA2) for these func-
tions are AA2-X28:3-11. Each function connects to any input
and GND (AA2-X29).
8
9
10
7
6
5
AUX6
AUX7
AUX8
AUX5
AUX4
AUX3
AA2-X28AA2-X29
GND
S1156 External
The example above uses the inputs AUX1 (AA2-X28:3) and AUX2 (AA2-X28:4).
Selectable outputs
A selectable output is AA2-X27.
The output is a potential-free switching relay.
If S1156 is switched off or in emergency mode, the relay is
in C-NC position.
123
K10
NO
C
NC
AA2-X27
External
S1156
Caution
The relay output may be subjected to a max load
of 2 A at resistive load (230 V~).
TIP
The AXC accessory is required if more than one
function is to be connected to the AUX output.
NIBE S1156Chapter 5 | Electrical connections26