B alarm
In the event of a B alarm the green light lights up on the front and a symbol with a service technician is displayed in
the information window until the alarm is reset. All alarms are automatically reset if the cause is rectified.
May be due toActionCauseAlarm text on the
display
Alarm no.
Alarm 101-120. See A-alarm 1-20.Sensor fault BT1101
Sensor fault BT3103
Sensor fault BT6106
Resets automatically when the
sensor has worked continuously
for 60 s.
Replace display
of BT7 temperat-
ure with ”---”
Sensor temporar-
ily missing
Sensor fault BT7107
Sensor fault BT12112
Sensor fault BT14114
Sensor fault BT15115
Sensor fault BT16116
Sensor fault BT17117
Sensor fault BT20120
See alarm 50.Temporary HP alarm150
The temperature of BT12 has ex-
ceeded 59 ºC. The alarm is reset
when the Temperature has
dropped below 59 ºC and condens-
er return (BT3) has dropped 2K
since the alarm.
High condenser out162
The return temperature (BT3) has
exceeded 58 °C. It is reset when the
temperature has dropped to 56 ºC.
High condenser in163
Suggestion: Check electrical anode,
circuit board at the electrical anode
as well as cables to the electrical
anode.
Electrical anode
fault
Electrical anode incor-
rect
166
Temporary communication fault.
See alarm 70.
Com. error input card170
Temporary communication fault.
See alarm 71.
Com. error base card171
Temporary communication fault.
See alarm 73.
Com. error heating
system2
173
Temporary communication fault.
See alarm 74.
Com. error heating
system3
174
Temporary communication fault.
See alarm 76.
Com. error heating
system4
176