Parameter: E08
Description: Indoor temp. calibration.
Available settings: -9.0~+9.0
Default setting: 0.0
Parameter: E10
Description: Externaltemp. calibration.
Available settings: -9.0~+9.0
Default setting: 0.0
Parameter: E11
Description: Function option of external temp. sensor.
0: External temperature sensor work as high temperature protection detection
1: External temperature sensor work as main control temperature
Available settings: 0~1
Default setting: 0
Parameter: E12
Description: Anti-Freeze protection switch.
ON: Turn on
OFF: Turn off
Default protection temperature range: (5.0°C - 8.0°C)
Anti-Freeze feature is available only when heating mode,
turn on when temperature decrease to 5.0°C, turn off when temperature increase to 8.0°C
Available settings: ON / OFF
Default setting: OFF
Parameter: E13
Description: Fan mode option when indoor
temperature reaches to setting temp.
ON: fan keep low speed
OFF: fan turned off
Available settings: ON/OFF
Default setting: OFF
Parameter: E14
Description: Fan working mode.
0: Fan works both for cooling and heating mode
1: Fan works only in cooling mode
2: Fan works only in heating mode
3: Fan not work neither in cooling nor heating mode
Available settings: 0~3
Default setting: 0