EN - Instructions and warnings for installation and use
Z-Wave Fan Coil Thermostat for 4-pipe installations
Fan4-Control
Nice
v.1.5
Question and Answer IconNeed help?

Do you have a question about the Nice Fan4-Control and is the answer not in the manual?

Summary

Warnings and General Precautions

Product Specification

Installation

Wiring Diagram

Fan4-Control Wiring Diagram

Details the wiring connections for the Fan4-Control unit.

Buttons and Display

Fan4-Control Display Screen

Explains the Fan4-Control device's display screen elements and icons.

Fan4-Control Operational Buttons

Describes the function of each operational button on the Fan4-Control device.

Modes of Operation

Parameter Menu

Parameter E01: Restore to factory default

Restores the device to its original factory settings.

Parameter E02: Power on state after power failure

Configures the device's state after an electrical power interruption.

Parameter E12: Anti-Freeze Protection

Enables or disables the anti-freeze protection feature.

Adding; Removing Fan4-Control from Z-Wave Network

Adding Device Using the Manual Method

Step-by-step guide to manually add the device to a Z-Wave network.

Adding Device Using the SmartStart Method

Instructions for adding the device via the SmartStart feature.

Removing Device from Yubii Home

Procedure for excluding the device from the Z-Wave network.

Association Group

Supported Z-Wave Command Classes

Z-Wave Parameter Setting

Parameter 12: Power Failure Memory (E02)

Determines device state after power interruption.

Parameter 22: Anti-Freeze Protection (E12)

Activates or deactivates the anti-freeze protection.

Parameter 255: Factory Restore (E01)

Initiates a factory reset procedure.

Overview

The Nice Fan4-Control is a Z-Wave (800 series) enabled fan coil thermostat designed for indoor temperature control in 4-pipe fan coil systems. It can read room temperature and automatically control fan speed based on the temperature difference. This product is compatible with Nice hubs equipped with Z-Wave radio, such as Yubii Home, Yubii Home Pro, FIBARO Home Center 3 Lite, and Home Center 3.

Function Description

The Fan4-Control thermostat offers various operational modes and settings to manage your fan coil system effectively.

On/Off Setting: When powered on, the device displays "OFF." Press the power button to enter the working interface. To turn it off, press the power button again; "OFF" will be displayed, and all outputs will be turned off.

Timing Power Off: To set a timing power off, turn the device on, then long press the power button and the mode button simultaneously for 3 seconds. This will enter the timing setting interface. Use the up or down arrows to adjust the setting value, then press the mode button to save the setting and return to normal operation. The timing icon "OFF" will be displayed on the screen. The setting range is 00:30-12:00, with a half-hour gap and a minimum unit of half an hour. To cancel timing power off, manually turn the device Off/On or set the timer value to 00:00.

Panel Lock: To activate or deactivate the key lock, long press the up and down arrows simultaneously for 3 seconds. This function is available even in Off mode. When the key protection icon appears on the screen, it indicates that the keys are locked, and all key operations are ignored. If the icon is not present, all key actions are available. This function can be disabled by setting parameter E15 to Off.

Fan Speed Setting: During normal operation, press the fan speed change button to switch among available fan speeds: "Low," "Medium," "High," and "Auto." In Ventilation mode, the "Auto" speed choice is not available.

Auto Fan Speed Mode: In this mode, the fan speed automatically adjusts based on the difference between the setpoint temperature and the actual room temperature. The fan is activated only when the valve is opened.

Fan Automation:

  • Cooling Mode: If the room temperature is less than or equal to the setting temperature, the valve closes automatically, and the fan stops. If the room temperature is greater than the setting temperature by +1°C, the fan turns on in low speed. At +2°C, it turns on in medium speed, and at +3°C, it turns on in high speed.
  • Heating Mode: If the room temperature is greater than or equal to the setting temperature, the valve closes automatically, and the fan stops. If the room temperature is less than the setting temperature by -1°C, the fan turns on in low speed. At -2°C, it turns on in medium speed, and at -3°C, it turns on in high speed.
    • Note: Unless parameter E13 is switched to ON, the fan stops when the room temperature reaches the setting temperature. The fan operates only if the valve opens.

Temperature Setting: During normal operation, use the up or down arrows to adjust the setpoint temperature. The default range is 5 to 37 degrees Celsius, with each button press changing the value by 0.5°C. Press the mode button to confirm the setting, or wait for 8 seconds without any operation for the device to automatically return to normal working interface and save the modification. When setting the temperature in Auto mode, press the mode button to switch between Cooling and Heating modes, then use the up or down arrows to save the setting and return to normal working interface.

Temperature Sensor Error: If the temperature sensor malfunctions, "0.0" will be displayed, the fan will stop, and the valve will close automatically.

Working Mode Setting: Under the normal working interface, press the mode button to switch between cooling, heating, and ventilation modes sequentially.

Fan Manual Control: If the fan speed is manually set, the device still auto-controls the fan in the following situations:

  • Cooling Mode: If room temperature is less than or equal to the setting temperature, the valve closes, and the fan stops. If room temperature is greater than or equal to the setting temperature +1°C, the valve and fan open.
  • Heating Mode: If room temperature is greater than the setting temperature, the valve closes, and the fan stops. If room temperature is less than or equal to the setting temperature -1°C, the valve and fan open.
  • Ventilation Mode: The fan operates normally according to the set fan speed, and the valve is forced to close. The fan output is independent of the setting temperature in ventilation mode, and auto fan speed mode functions are not available.

Manual Fan Speed Mode: If the fan speed is manually set, it can be overridden in certain conditions to stop the fan:

  • Cooling Mode: When room temperature is less than the setpoint temperature, the valve closes, and the fan stops. When room temperature is greater than the setpoint temperature +1°C, the valve and fan start (with the manually set speed).
  • Heating Mode: When room temperature is greater than the setpoint temperature, the valve closes, and the fan stops. When room temperature is less than the setpoint temperature -1°C, the valve and fan start (with the manually set speed).
  • Ventilation Mode: The fan works according to the set fan speed, and the valve is forced to close. The fan speed is independent of the setpoint temperature in ventilation mode since auto mode is not available.

Auto Mode: If room temperature is greater than or equal to the setting temperature +1°C, the fan turns on, the heat valve closes, and the cool valve opens. If room temperature is less than or equal to the setting temperature -1°C, the fan turns on, the heat valve opens, and the cool valve closes.

Maintenance Features

Parameter Menu: When the device is turned off, long press the mode button and the up arrow simultaneously to enter the Parameter Menu. Input password "5138," changing digits with the up or down arrows and moving between digits with the fan speed change button. Confirm the PIN by pressing the mode button.

Factory Restore (E01): This parameter allows restoring the device to factory default settings. Change the value to "55" to initiate the restore process, which will also turn off the device.

Power on state after power failure (E02):

  • "0": Device does not return to the previous mode and stays switched off.
  • "1": Device returns to the previous mode and stays switched on.
  • "2": Device returns to the last mode (Off/Heating/Cooling/Ventilation).

Backlight brightness (E03):

  • "1": Backlight is off on dimmed display after a specific time of no key action.
  • "2": Low brightness and dimmed display after a specific time of no key action.
  • "3": Medium brightness and dimmed display after a specific time of no key action.
  • "4": High brightness and dimmed display after a specific time of no key action.
  • "5": Display always on.

Beep volume (E04):

  • "1": OFF
  • "2": Low Beep
  • "3": Medium Beep
  • "4": High Beep
  • "5": Standard Beep

Communicate address (E05): Sets the communication address (1-64).

Temperature limits (E06, E07): Sets the upper and lower limits for temperature (0.0°C-55.0°C).

Temperature calibration (E08, E10): Allows for indoor and external temperature calibration (from -9.0 to +9.0).

External temp. sensor function (E11):

  • "0": External temperature sensor works as high-temperature protection detection.
  • "1": External temperature sensor works as the main control temperature.

Anti-Freeze protection switch (E12):

  • "ON": Turns on anti-freeze protection.
  • "OFF": Turns off anti-freeze protection.
    • The default protection temperature range is 5.0°C - 8.0°C. This feature is available only in heating mode. It turns on when the temperature decreases to 5.0°C and turns off when it increases to 8.0°C.

Fan mode option when indoor temp. reaches to setting temp (E13):

  • "1": Manual fan speed, keeps fan speed, valve turned off, Auto fan speed, keeps low fan speed.
  • "0": Fan turned off.

Fan working mode (E14):

  • "0": Fan works both for cooling and heating mode.
  • "1": Fan works only in cooling mode.
  • "2": Fan works only in heating mode.
  • "3": Fan does not work in neither cooling nor heating mode.

Panel lock function (E15):

  • "ON": Turns on panel lock.
  • "OFF": Turns off panel lock.

Interval ventilation feature (E17, E18):

  • "ON": Turns on interval ventilation.
  • "OFF": Turns off interval ventilation.
    • Duration for interval ventilation can be set from 1 to 30 minutes.

Temperature deadband (E19): Sets the temperature deadband (°C or °F), with an accuracy of n*0.1 (0-9.9).

Temperature unit (E20):

  • "0": Celsius
  • "1": Fahrenheit

Adding/Removing from Z-Wave Network

Manual Method:

  1. Set the Yubii Home into add mode.
  2. On the thermostat's home page, long press the up arrow and mode button simultaneously for 3 seconds. The Fan4-Control will enter adding mode, displaying "--" on the interface. If a number is displayed, the device is already added; remove it first or restore factory defaults.
  3. Press the mode button to include the device into the Z-Wave network. Upon successful inclusion, the node number will be displayed.

SmartStart Method:

  1. Scan the DSK QR code or input the 5-digit PIN code (found on the box and device).
  2. Power on the device (turn on mains voltage).
  3. Successful adding will be confirmed by the Z-Wave indicator on the display.

Removing Device:

  1. Set the Yubii Home into exclusion mode.
  2. On the thermostat's home page, long press the up arrow and mode button simultaneously for 3 seconds. The Fan4-Control will enter removing mode, displaying the existing product ID.
  3. Press the mode button to exclude the device from the Z-Wave network. Upon successful exclusion, "000" will be displayed.

Nice Fan4-Control Specifications

General IconGeneral
DisplayLCD
TypeThermostat
Control TypeTouch
Operating Temperature0°C to +50°C
Humidity Range5% - 95% RH, non-condensing
Dimensions140 x 90 x 30 mm
Weight200g