Nidec Commander C300 - Calculating the Air-Flow in a Ventilated Enclosure

Nidec Commander C300
124 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Unidrive M / HS Frame 7 to 10 Power Installation Guide 37
Safety information Product information
Mechanical installation
Electrical installation Technical data UL listing information
Where:
V Air-flow in m
3
per hour (1 m
3
/hr = 0.59 ft
3
/min)
T
ext
Maximum expected temperature in
C outside the enclosure
T
int
Maximum permissible temperature in C inside the enclosure
P Power in Watts dissipated by all heat sources in the enclosure
k Ratio of
Where:
P
0
is the air pressure at sea level
P
I
is the air pressure at the installation
Typically use a factor of 1.2 to 1.3, to allow also for pressure-drops in dirty air-filters.
Example
To calculate the size of an enclosure for the following:
Three drives operating at the Normal Duty rating
External EMC filter for each drive
Braking resistors are to be mounted outside the enclosure
Maximum ambient temperature inside the enclosure: 40 C
Maximum ambient temperature outside the enclosure: 30 C
For example, dissipation of each drive: 101 W and dissipation of each external EMC filter: 6.9 W
(max).
Total dissipation: 3 x (101 + 6.9) = 323.7 W
Insert the following values:
T
int
40 C
T
ext
30 C
k 1.3
P 323.7 W
Then:
= 126.2 m
3
/hr (74.5 ft
3
/min) (1 m
3
/ hr = 0.59 ft
3
/min)
P
o
P
l
-------
V
31.3 323.7
40 30
---------------------------------------
=