EasyManua.ls Logo

Nidec Commander C300 - Terminal Size and Torque Settings; Drive Control Terminal Data; Drive Power Terminal Data

Nidec Commander C300
124 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
48 Unidrive M / HS Frame 7 to 10 Power Installation Guide
3.10 Terminal size and torque settings
Table 3-13 Drive control terminal data
Table 3-14 Drive relay terminal data
Table 3-15 Terminal block maximimum cable sizes
Table 3-16 Maximum crimp/lug sizes for frame size 8 to 10
Table 3-17 Drive power terminal data
Model Connection type Torque setting
M200 to M400 Screw terminals 0.2 N m (0.15 lb ft)
M600 to M702 Plug-in terminal block 0.5 N m (0.4 lb ft)
Model Connection type Torque setting
M200 to M400 Screw terminals
0.5 N m (0.4 lb ft)
M600 to M702 Plug-in terminal block
Model
Size Terminal block description Maximum cable size
All All Control connector
1.5 mm
2
(16 AWG)
All All 2 way relay connector
2.5 mm
2
(14 AWG)
M300 to M400 7 to 9 STO connector
M600 to M702 All
2 way low voltage power 24V supply
connector
1.5 mm
2
(16 AWG)
Terminals
Maximum standard crimp (mm
2
)
Maximum standard US lug
(kcmil)
AC supply connections 2 x 185 2 x 500
AC supply ground 2 x 120 1 x 350
Motor connections 2 x 150 2 x 350
Drive output ground 2 x 150 1 x 350
Brake connection 2 x 150 2 x 350
Model
size
AC and motor terminals DC and braking Ground terminal
Recommended Maximum Recommended Maximum Recommended Maximum
7
M8 Nut (13 mm AF) M8 Nut (13 mm AF) M8 Nut (13 mm AF)
12 N m
(8.85 lb ft)
14 N m
(10 lb ft)
12 N m
(8.85 lb ft)
14 N m
(10 lb ft)
12 N m
(8.85 lb ft)
14 N m
(10 lb ft)
8 to 10
M10 Nut (17 mm AF) M10 Nut (17 mm AF) M10 Nut (17 mm AF)
15 N m
(11.1 Ib ft)
20 N m
(14.8 Ib ft)
15 N m
(11.1 Ib ft)
20 N m
(14.8 Ib ft)
15 N m
(11.1 Ib ft)
20 N m
(14.8 Ib ft)

Other manuals for Nidec Commander C300

Related product manuals