NE200/300 Series Drive User Manual
166 Chapter 6 Parameter description
F8.25 PID feedback offline
detection time
Range: 0.0~50.0s2.0s
F8.26 PID feedback offline
detection Min. Frequency
Range: 0.00~50.00Hz10.00Hz
When the running frequency is higher than F2.26 and feedback signal is
lower than F8.24 for a period of time defined by F8.25, the drive will give
alarm (PID offline).
6.10 PLC and Multi-steps group (F9)
F9.00 Multi-step freq. 1 Range: 0.00Max frequency5.00Hz
F9.01 Multi-step freq. 2 Range: 0.00Max frequency10.00Hz
F9.02 Multi-step freq. 3 Range: 0.00Max frequency15.00Hz
F9.03 Multi-step freq. 4 Range: 0.00Max frequency20.00Hz
F9.04 Multi-step freq. 5 Range: 0.00Max frequency30.00Hz
F9.05 Multi-step freq. 6 Range: 0.00Max frequency40.00Hz
F9.06 Multi-step freq. 7 Range: 0.00Max frequency50.00Hz
Define Multi-steps frequency respectively, which can be used in
Multi-step speed running and simple PLC running.
For Multi-steps speed running, Multi-step speed frequency can be
selected by multi-step terminals. While in simple PLC running, Multi-step
speed frequency is decided by present running step. It is shown in Fig.6-25.
F9.07 PLC running mode Range: 022
0: Single cycle 1
The drive stops automatically after one cycle of operation and will start
when receiving RUN command again.
1: Single cycle and hold the final value
The drive will hold the operating frequency and direction of last step
after completing one cycle of operation.