NE200/300 Series Drive User Manual
Chapter 5 List of Parameters 89
Code
Description Setting range Default
Modify
Modbus
Address
120%
FC.08
Input phase loss
detection
1
100%
(100% correspond
to 800V)
20% × 0D08H
FC.09
Input phase loss
detection delay
time
2
255s 10s × 0D09H
FC.10
Output phase loss
detection
0:
Invalid
1: Valid 1 0D0AH
FC.11
Terminal close
fault detection
0:
Invalid
1: Valid 1 0D0BH
FC.12
Fault auto reset
times
0
10,“0” means
auto reset is
disabled. Only 3
faults have auto
reset function
0 × 0D0CH
FC.13
Fault auto reset
interval
0.1
20.0s/time 5.0s × 0D0DH
FC.14
Under-voltage
fault treatment
0: No treatment
1: Auto reset at
power recovery
2: Auto run at power
recovery (Auto run
time interval is
F1.16)
0 0D0EH
FC.15
Fast current limit
50.0%~100.0%
(100% means this
function is disabled.)
Depends
on
model
0D0FH
FC.16
Fast current limit
time
0.01~1.00s 0.10s 0D10H
FC.17
Overvoltage
suppression freq.
0.00~10.00Hz 0.00Hz
0D11H
FC.18
Select
suppression
0: method 1
1: method 2
0 0D12H