EasyManua.ls Logo

Nidec Unidrive M600 - Drive Objects and Speed;Torque Control

Nidec Unidrive M600
216 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SI-Ethernet User Guide 187
Issue: 3
Safety
information
Introduction
Mechanical
installation
Electrical
installation
Getting started Parameters
Key features
and Protocols
PC Tools
Applications
Security Diagnostics
Glossary of
terms
Index
7.5.21 AC/DC Drive object
Class: 0x2A (42
10
)
The AC/DC Drive object provides information on the drive running state and supports the following
attributes:
AtReference
Indicates that the drive is running at the requested speed.
Get Pr 0.10.006
0 = Drive not running at requested speed.
1 = Drive running at requested speed.
Table 7-31 AC/DC Drive object attributes
Attribute
ID
Name Access Parameter dependence
0x03 (3
10
)
AtReference Get
Pr 0.10.006
0x04 (4
10
)
NetRef Get/Set
Pr 0.06.042 (bit 8)
0x06 (6
10
)
DriveMode Get/Set
(See Table 7-32 on page 188)
0x07 (7
10
)
SpeedActual Get
RFC-A or
RFC-S
Pr 0.03.002
Open Loop Pr 0.05.004
0x08 (8
10
)
SpeedRef
Get/Set
RFC-A or
RFC-S
Pr 0.01.021
(scaled to 0 decimal places)
Get Open Loop
Pr 0.01.021 * 60 / NofPP
(scaled to 0 decimal places)
Set Open Loop
Pr 0.01.021 = SpeedRef *
NofPP / 60
(scaled to 0 decimal places)
0x0B (11
10
)
TorqueActual Get
Pr 0.04.020
(scaled to 1 decimal place)
0x0C (12
10
)
TorqueRef Get/Set
Pr 0.04.008
(scaled to 1 decimal place)
0x1D (29
10
)
RefFromNet Get
1Pr 0.01.049=3 AND Pr 0.01.050=1
0Pr 0.01.049<>3 OR Pr 0.01.050<>1
NofPP = Number of Pole Pairs.
Name: AtReference
Class 0x2A Default N/A
Instance 0x01 Data Type USINT
Attribute 0x03 Access Get
NOTE