SI-Ethernet User Guide 127
Issue: 3
Safety
information
Introduction
Mechanical
installation
Electrical
installation
Getting started
Parameters
Key features
and Protocols
PC Tools
Applications
Security Diagnostics
Glossary of
terms
Index
6.1.10 Menu 23– EtherNet/IP Fault Values
This menu contains the parameters used to define the values to be sent to the mapped output
destinations when fault values have been configured to be sent after either a RPI timeout event
(see RPI timeout action (S.20.011), RPI timeout event destination (S.20.012) and RPI timeout
event type (S.20.013)) or a PLC idle event (see PLC idle action (S.20.015), PLC idle event
destination (S.20.016) and PLC idle event type (S.20.017)) has occurred.
S.22.031 Output mapping parameter 31
Minimum
0
(Display: 0.00.000)
Maximum
499999
(Display: 4.99.999)
Default
0
(Display: 0.00.000)
Units None
Type 32 Bit User Save Update Rate
Module reset, EtherNet/IP
interface reset or EtherNet/IP
interface enable
Display Format Slot Menu Param Decimal Places 0
Coding RW, PT, BU
S.22.032 Output mapping parameter 32
Minimum
0
(Display: 0.00.000)
Maximum
499999
(Display: 4.99.999)
Default
0
(Display: 0.00.000)
Units None
Type 32 Bit User Save Update Rate
Module reset, EtherNet/IP
interface reset or EtherNet/IP
interface enable
Display Format Slot Menu Param Decimal Places 0
Coding RW, PT, BU
S.23.001 Output fault value 1
Minimum -2147483648 Maximum 2147483647
Default 0 Units
Type 32 Bit User Save Update Rate
Module reset, EtherNet/IP
interface reset or EtherNet/IP
interface enable
Display Format None Decimal Places 0
Coding RW, PT