90 SI-Ethernet User Guide
Issue: 3
This parameter defines the action to be taken when a late synchronized frame is received on the
Rx3 link.
Defines the destination (slot) to trigger the event when a late synchronized frame is received on the
Rx3 link.
S.11.060 Rx3 Late Sync Frame Action
Minimum
1
(Display: Trip)
Maximum
3
(Display: Use)
Default
1
(Display: Trip)
Units None
Type 8 Bit User Save Update Rate Read on reset
Display Format None Decimal Places 0
Coding RW, Txt, BU
Value Text Description
1 Trip Trip drive with Slx.Er and sub-trip code 107
2 Do not use The data is ignored
3 Use The data is used immediately
S.11.061 Rx3 Late Sync Frame Dest
Minimum
0
(Display: This slot)
Maximum
4
(Display: Slot 4)
Default
0
(Display: This slot)
Units None
Type 8 Bit User Save Update Rate Read on reset
Display Format None Decimal Places 0
Coding RW, Txt, BU
Value Text Description
0 This slot Trigger module event in this slot
1 Slot 1 Trigger module event in slot 1
2 Slot 2 Trigger module event in slot 2
3 Slot 3 Trigger module event in slot 3
4 Slot 4 Trigger module event in slot 4
This feature is not yet implemented.