92 SI-Ethernet User Guide
Issue: 3
This parameter allows the Modbus protocol to be defaulted to factory settings. This includes all of
the protocol features, configuration, mappings and stored objects.
This parameter will indicate any Modbus configuration errors.
This parameter can be changed from its default port of 502, however it is the user's responsibility to
ensure that a valid port is set.
S.15.003 Default
Minimum 0
(Display: Off)
Maximum
1
(Display: On)
Default 0
(Display: Off)
Units None
Type 1 Bit Volatile Update Rate
On module reset, protocol
interface reset or protocol
enable
Display Format None Decimal Places 0
Coding RW, NC
S.15.004 Modbus Config Error
Minimum 0
(Display: No error)
Maximum
3
(Display: Num Connections)
Default None Units None
Type 8 Bit Volatile Update Rate
Module reset, Modbus
interface reset or Modbus
interface enable
Display Format None Decimal Places 0
Coding RO, Txt, NC, ND, PT, BU
Value Text Description
0 No error No error
1 Port in use Specified port is currently in use by another protocol
2 Timeout event Timeout trigger event location is not valid
3 Num Connections
The Max priority connection is greater than the max
connections
S.15.005 Modbus Listening Port
Minimum 0 Maximum 65535
Default 502 Units None
Type 16 Bit User Save Update Rate
See Priority Protocol
(S.02.020)
Display Format None Decimal Places 0
Coding RW, BU