NIetz Electric Co.,Ltd
Soft starter SSN/SSA serie User Manual
25
9.8 Special parameter
●
Rate Current
The Rate Current indicate that the output current of the soft starter at the rate power. This parameter
changes with the output power of the soft starter. For detail see chapter 10. The methods shows below.
On READY state Sr8rdy, press ▼ key and not release, IE8888 displays on the keyboard, the unit is
ampere. Release this key, system return to READY state.
For Example : rate current is 150A
Rate current
Figure 9-6
●
Last Fault
On READY stateSr8rdy, press STOP key and release it 5 minutes later, the last fault code display
on the keyboard Er8888. Release the key, return READY state.
For example: the last fault is missing phase
fault code
Figure 9-7
Press STOP (maintain 5 seconds)
Sr
8
rdy
Er
8
101
press▼
Sr
8
rdy
IE
8
150