EasyManua.ls Logo

nilan Compact P CTS700 - Fan System Operation; Fan Speed - Level Adjustment; Fan Speed - Humidity Control; Fan Speed - Cooling Function

nilan Compact P CTS700
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
We reserve the right to make changes
10
Fan
UserSuperuser
Fan speed - Fan level
It is possible to turn the ventilation up and down as needed.
Ventilation levels are set in the Fan menu:
• Fan The ventilation can be set between 20 and 100%.
NB! Remember at what % the system runs basic ventilation.
Fan speed - Humidity control
As standard, Compact P has intelligent humidity control, to ensure an optimum humidity level at all times.
Humidity control is set in the Fan menu:
• Low RH setpoint (%) Set at which humidity level low ventilation is to be initiated.
Adjustable between 15 and 45% (factory setting: 30%)
• Low speed at low RH (%) You can set the fan speed at low air humidity.
Adjustable between 20 and 80% (factory setting: 25%).
High speed at high RH You can set the fan speed at high air humidity.
Adjustable between 30 and 100% (factory setting: 75 %).
The high humidity function runs for minimum 15 minutes.
• Average Monthly RH (%) States the average humidity, RH (%) measured over the last 24 hours.
It is possible to test the high humidity function by changing the relative humidity.
Fan speed - By cooling function
Compact P can cool with the help of a bypass function, cooling energy recovery and compressor.
Increasing the ventilation increases the cooling effect.
Cooling function is set in the Fan menu:
• High fan speed enabled High fan speed during cooling can be switched ON and OFF
(factory setting: Off).
• Fan speed high (%) You can set the fan speed during passive cooling.
Adjustable between 20 and 100 (factory setting: 80%).

Table of Contents