EasyManua.ls Logo

nilan Compact P CTS700 - Settings - Temperature Control

nilan Compact P CTS700
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
We reserve the right to make changes
16
Fan
Installer
Settings - Temperature control
For optimum operation, there are various temperature control settings, which can be adjusted.
Temperature control is set in the Temperature menu:
• CP/Master sensor You can select one of two sensors:
• T3: Temperature sensor – extracted air
• TPanel: Temperature sensor in the control panel
(factory setting: T3)
• CP/Regulate deadband (°C) Enter regulation neutral zone for temperature regulation
(factory setting: 1°C)
• CP/Bypass damper offs.(°C) Set regulation offset value for bypass damper
(factory setting: 0°C)
• CP/Cooling offset (°C) Offset temperature for cooling mode
(factory setting: 2°C)
Example:
20°C
• Night setback temp (°C) Increases setting of regulating neutral zone for heating operation, when the
system switches to night-time drop.
Example: When set at 3°C, heating will not start until 15°C.
Night lowering can be activated via the week programme or user selection.
• CP/EHD/BAH setp. offset (°C) Enter regulation offset for the EHD/BAH damper.
EHD: Switches between outdoor air through roof cowl or ground pipe.
BAH: Leads outdoor air through or past the heat exchanger
-connected ground pipes.
• CP/Compensation balance (%) Enter room vs. outdoor air compensation in accordance with predetermined graphs.
0% = only room compensation
100% = only outdoor air compensation
Regulation neutral zone 2°C
Regulation neutral zone 2°C
Offset for bypass 1°C
Offset for cooling 3°C
Room temp < 18°C starts active heating or heating coil (if any).
When the room temperature is > 25°C active cooling commences via the heat pump.
Room temp > 23°C open bypass

Table of Contents