28
Condenser curve control
Supply air [%]
Condenser temperature [°C]
> Low temp. compr. start Settings:
Standard setting:
Description:
0 -15 °C / Off / 0 15 °C
Off
Here you indicate whether the heat pump is to start up at low
outdoor temperatures, even if heating is not required.
Off means that the function has been deactivated.
> Level winter low Settings:
Standard setting:
Description:
Level 1 / Level 2 / Level 3 / Off
Off
Here you specify at what fan speed level you want the ventila-
tion unit to operate at low outdoor temperatures.
Off means that the function has been deactivated.
> Temperature winter low Settings:
Standard setting:
Description:
-20 10 °C
0 °C
Here you specify at which outdoor temperature the “Winter low”
function is to be activated.