All rights reserved Side 9 af 16
Output.CenHeatCap
203
100
%
Central heater capacity
VGU-VP
Output.CprCap
204
100
%
Compresor capacity
VPL-VPM-VGU-VP-
Compact
Output.PreHeatCap
205
100
%
Preheater capacity or earth tube
air intake fan speed
VPcCoB
Time.Second
300
ss
Second
All plants
Time.Minute
301
nn
Minute
All plants
Time.Hour
302
hh
Hour
All plants
Time.Day
303
dd
Day
All plants
Time.Month
304
mm
Month
All plants
Time.Year
305
yyyy
Year
All plants
Alarm.Reset
400
Clear one specific alarm code or
all
0 : No command
1..99 : (reserved internal
commands)
101..199 : Clear alarm display
code 1..99
255 : Clear all alarms
All plants
Program.Select
500
Week program nb. select
0 : None
1 : Program 1
2 : Program 2
3 : Program 3
4 : Erase
All plants
Program.UserFuncAc
t
600
User function active (See
“UserFuncSet”)
All plants
Program.UserFuncS
et
601
User function select
0 : None
1 : Extend
2 : Inlet
3 : Exhaust
4 : External heater offset
5 : Ventilate
6 : Cooker Hood
All plants
Program.UserTimeS
et
602
Min
Min User function period
All plants
Program.UserVentSe
t
603
Step
Step User function ventilation
0 : Off
1..4 : Step number
All plants
Program.UserTempS
et
604
100
°C
User function temperature
(Extend function only)
All plants
Program.UserOffsSet
605
100
°C
User function
temperature(Offset function
only)
All plants
Program.User2Func
Act
610
Same as user function 1 above
VPL-VGU-VP-Compact-
Comfort

Other manuals for nilan CTS 602

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the nilan CTS 602 and is the answer not in the manual?

nilan CTS 602 Specifications

General IconGeneral
Brandnilan
ModelCTS 602
CategoryControl Panel
LanguageEnglish

Related product manuals