Input registers:
Name
Addres
s
Scale
Unit
Description
Used to plant type
Bus.Version
000
Protocol version number
All plants
App.VersionMajor
001
text
Software version - major (2
character ascii text)
All plants
App.VersionMinor
002
text
Software version - minor (2
character ascii text)
All plants
App.VersionRelease
003
text
Software version - release (2
character ascii text)
All plants
Input.UserFunc
100
User function
All plants
Input.AirFilter
101
Air filter alarm
VPM-Comfort-Comforti
Input.DoorOpen
102
Door contact
VPM-Comforti
Input.Smoke
103
Fire/Smoke alarm
All plants
Input.MotorThermo
104
Motor thermo fuse
VPM-Comforti
Input.Frost_Overht
105
Heating surface frost /
overheat
VPL-VPM-Compact-
Comfort-Comforti
Input.AirFlow
106
Airflow monitor (guard)
VPL-VPM-Compact-
Comfort-Comforti
Input.P_HI
107
High pressure switch
All Plants
Input.P_LO
108
Low pressure switch
Not in use
Input.Boil
109
Hot water boiling
VGU-VP-Compact
Input.3WayPos
110
Hot water 3-way valve position
Not in use
Input.DefrostHG
111
Hotgas defrost type selection
Not in use
Input.Defrost
112
Defrost thermostat
VPL-VPM-VGU-VP-
Compact
Input.UserFunc_2
113
User function 2
VPL-VGU-VP-Compact-
Comfort
Input.DamperClosed
114
Air damper closed position
Comfort-COMFORTi
Input.DamperOpen
115
Air damper opened position
Comfort-COMFORTi
Input.T0_Controller
200
100
°C
Controller board temperature
All plants
Input.T1_Intake
201
100
°C
Fresh air intake temperature
VPL-VPM-VGU-VP-
Compact
Input.T2_Inlet
202
100
°C
Inlet temperature (before
heater)
VPL-VPM-VP-Compact-
Comfort-Comforti
Input.T3_Exhaust
203
100
°C
Room exhaust temperature
Comfort-Comforti
Input.T4_Outlet
204
100
°C
Outlet temperature
Compact-Comfort-
Comforti
Input.T5_Cond
205
100
°C
Condenser temperature
VPL-VPM-VP-Compact
Input.T6_Evap
206
100
°C
Evaporator temperature
VPL-VPM-VGU-VP-
Compact
Input.T7_Inlet
207
100
°C
Inlet temperature (after heater)
VPL-VPM-VP-Compact-
Comfort-Comforti
Input.T8_Outdoor
208
100
°C
Outdoor temperature
Comfort-Comforti