Cooling high ventilation step
VPL-VPM-VP-Compact-
Comfort-Comforti
Select weekly air damper
position self-test
Once enabled, the
function cannot be
deactivated
0: Off
1: Wednesday 0400
2: Wednesday 1200
Date of last air damper position
test Bit word packed in DOS
date format (see IR 402 format)
Actual air damper position test
state 0: Off
1: Standby
2: Start(Set to Start to run
manual test)
3: Closing
4: Opening
5: OK
6: Error
Cooling temperature setpoint
select
0 : Off (No cooling allowed)
1 : Set + 0 °C (User setpoint
plus 0 degrees)
2: Set + 1 °C
3: Set + 2 °C
4: Set + 3 °C
5: Set + 4 °C
6: Set + 5 °C
7: Set + 7 °C
8 : Set + 10 °C
VPL-VPM-VP-Compact-
Comfort-Comforti
VPL-VPM-VP-Compact-
Comfort-Comforti
VPL-VPM-VP-Compact-
Comfort-Comforti
VPL-VPM-VP-Compact-
Comfort-Comforti
Outdoor day temperature for
night cooling activation [0:Off,
20..40]
Free energy night cooling room
setpoint [10..30]