28 BU 0630 en-2020
3 Assembly and installation
The installation instructions contained in this manual only deal with issues that are related to functional
safety. For further information, please refer to the manual for the relevant frequency inverter (BU
0600).
Pos: 123 /A nleit ung en/El ek tr onik /Saf ety /4. M on tage un d I nstal la tio n/Ei nbau u nd Mont age_0 1 @ 15\mod_1485429630421_388.docx @ 2316175 @ 2 @ 1
3.1 Installation and assembly
The installation instructions in BU 0600 must be observed!
Pos: 12 4 /Anlei tung en/El ektr onik/S afety /4. Mon tage un d Instal lati on/Ei nbau u nd Mont age_0 2 [SK 5xx E] @ 15\mod_1485429733283_388.docx @ 2316211 @ @ 1
The frequency inverter must comply with protection class IP20. It must be installed in an adequately
ventilated installation space with protection class IP54 (or higher).
Pos: 12 5 /Tech nisc he Inform ati onen/S onsti ge Dok ument e/TI 80 _003 0 - Funkti onale S icher heit NOR DAC PR O SK 5xx P/Mo ntage einer Kun dens chnitts tell e SK CU5 [S K 500P ] @ 44\mod_1593173350122_388.docx @ 2638821 @ 3 @ 1
3.1.1 Assembly of an SK CU5-STO and SK CU5-MLT customer unit
DANGER
Danger of electric shock
The frequency inverter has a hazardous voltage for up to 5 minutes after it has been switched off.
Only carry out work when the frequency inverter has been disconnected and at least 5 minutes
have elapsed since the mains was switched off!
Installation must be carried out as follows:
1. Switch off the mains voltage, observe the waiting period.
2. Push the control terminal cover down and remove it.
3. Remove the blank cover by activating the release mechanism at the lower edge and removing it
with an upward rotating movement.
4. Break out the internal jumper of the STO contact with the aid of a small screwdriver or small
needle-nose pliers. Otherwise the customer unit cannot be installed.
Information
Once the jumper has been removed, the frequency inverter cannot be operated with functional safety
without CU5.
5. Hook the customer unit onto the upper edge and press in lightly until it engages. Take care that the
connector strip makes proper contact.
6. Install the control terminals and blank cover.