Functional SafetySupplementary manual for series SK 500P
56 BU 0630 en-2020
8 Technical Data
Pos: 34 8 /Anlei tu nge n/El ektr onik /S afety /1 0. T ech nisc he Da ten/T ec hnisc h e Dat en _02 @ 1 7\mod_1488804807584_388.docx @ 2333179 @ @ 1
The Technical Data from the frequency inverter manual (BU 0600) apply!
In deviation from this:
Function Specification
Max. installation altitude
above sea level
2000 m
The following technical data also apply.
Pos: 34 9 /Allg emein/ Allg emeing ültig e Mod ule/---------Sei tenum bruc h k omp akt --------- @ 13\mod_1476369695906_0.docx @ 2265495 @ @ 1
Pos: 353 /T echni sche In form ationen /So nstige D okum ente/T I 80_00 30 - Fun ktion ale Sic herhei t NORD AC PRO SK 5xxP/T echni sche Daten: Sicher e Pulss perre u nd safe ty Digi taleing ang @ 44\mod_1594131305701_388.docx @ 2643656 @ 2 @ 1
8.1 Safe Pulse Block and Safety Digital Input
Safe Pulse Block Safety Digital Input
SK 510P, SK 540P SK CU5-STO or
SK CU5-MLT
(SK 530P, SK 550P)
SK 510P and SK 540P,
SK CU5-STO or SK CU5-
MLT (530P, SK550P)
Input voltage
+24 V ±25% (18 V … 30 V) +24 V -37.5% +25%
(15 V … 30 V)
Operation with OSSD
-20% … +25% (19.2 V … 30 V)
+24 V -37.5% +25%
(15 V … 30 V)
High - level (VT+)
18 V
15 V
Low - level (VT-)
3 V
3 V
Current consumption (average
value)
Depending on the input voltage and
application class (inverter type and pulse
frequency) see 7.1.2 "Switching capacity
and current load"
10 mA
Peak current (peak, when
switching on or on the OSSD)
700 mA
VIS1: ≤ 70 mA
VIS2: ≤ 700 mA
25 mA
Input resistance
Low level: 10 kΩ
High level: 3 … 5
Input capacitance
approx. 30 µF
(downstream of
inverse polarity
protection)
VIS1: approx. 5 µF
VIS2: approx. 30 µF
(downstream of
inverse polarity
protection)
approx. 10 nF
Cable length
≤100 m (shielded for compliance with EMC requirements), see 3.3.3
"EMC"
Cable capacitance
20 nF per connected frequency inverter (≤ 4 nF * t
OSSD
/ 0,1 ms for t
OSSD
500 µs)
Requirements for OSSDs
Test pulse width
200 µs ≤ t
OSSD
≤ 500 μs, see 3.3.2 "Operation with OSSD"
Duty (High level)
90 %
Time between double pulses
2 * t
OSSD
(note the duty factor)
Switch-on delay
(time between input change from Low
to High level and the time at which
enabling of the frequency inverter is
possible.)
160 ms
25 ms
15 ms