Parameter
[factory setting]
Setting value / Description / Note Device Supervisor
Parameter
set
The basic equipment of SK 200E devices does not include an analog input. An analog function
can only be implemented by the use of options (Array [-01]...[-05]) or by use of the digital input 2
or 3 (Array [-06]...[-07]). The following settings are then possible:
0 = Off, the analog input has no function. After the FI has been enabled via the control
terminals, it will supply the set minimum frequency (P104).
1 = Set frequency, the given analog range (P402/P403) varies the output frequency between
the set minimum and maximum frequencies (P104/P105).
2 = Frequency addition **, the supplied frequency value is added to the setpoint.
3 = Frequency subtraction**, the supplied frequency value is subtracted from the setpoint.
4 = Minimum frequency, is a typical setting value for the function of the potentiometers P1 or
P2 (P400 [01] or [02]), which are integrated in the cover of the FI (Section 4.1.3).
5 = Maximum frequency
, is a typical setting value for the function of the potentiometers P1 or
P2 (P400 [01] or [02]), which are integrated in the cover of the FI (Section 4.1.3).
6 = PI actual value process controller *, activates the process controller, analog input 1 is
connected to the actual value sensor (compensator, air can, flow volume meter, etc.).
The mode (0-10 V or 0/4-20 mA) is set in P401.
7 = PI setpoint process controller *, as function 6, however the setpoint is specified (e.g. by
a potentiometer). The actual value must be specified using another input.
8 = PI controller, actual value*,
9 = PI controller, actual value limited*,
10 = PI controller, actual value monitored*,
11 = Torque current limit (limited), depends on parameter P112. This value corresponds to
100% of the setpoint value. Attainment of the set limiting value causes a reduction of the
output frequency at the limit of the torque current.
12 = Torque current limit (switch-off), depends on parameter P112. This value corresponds
to 100% of the setpoint value. The attainment of this set limiting value causes switch-off
with error code E12.3.
13 = Current limit (limiting), depends on parameter P536. This value corresponds to 100% of
the setpoint value. The attainment of the set limiting value causes a reduction of the
output voltage in order to limit the output current.
14 = Current limit (switch-off), depends on parameter P536. This value corresponds to 100%
of the setpoint value. The attainment of this set limiting value causes switch-off with error
code E12.4.
15 = Ramp time, is a typical setting value for the function of the potentiometers P1 or P2 (P400
[01] or [02]), which are integrated in the cover of the FI (Section 4.1.3).
16 = Torque precontrol, function which enables a value for the anticipated torque requirement
to be entered in the controller (interference factor switching). This function can be used to
improve the load take-up of lift equipment with separate load detection.
17 = Multiplication, the setpoint is multiplied with the analog value supplied. The analog value
adjusted to 100% then corresponds to a multiplication factor of 1.
*) For further details of the PI and process controller, please refer to the supplementary
description.
**) The limits of these values are set by the parameters >Minimum frequency auxiliary
setpoints< P410 and >Maximum frequency auxiliary setpoints< P411.