118 Subject to technical alterations BU 0200 GB
Parameter
[factory setting]
Setting value / Description / Note Device Supervisor
Parameter
set
19 = ... 29 reserved
For Posicon functions see BU 0210
30 = Digital-In 1 status*
High
Further details
in Bus Manual
BU 0250
31 = Digital-In 2 status*
High
32 = Digital-In 3 status*
High
33 = Digital-In 4 status*
High
39 = STO inactive *
High
*) P546...P548 = 17 or 19
P435 Standardisation of digital output
-400 ... 400 %
[ 100 ]
Adjustment of the limit values of the output function. For a negative value, the output function
will be output negative.
Reference to the following values:
Current limit (3) = x [%]
P203 >Rated motor current<
Torque current limit (4) = x [%]
P203 P206 (calculated rated motor torque)
Frequency limit (5) = x [%]
P201 >Rated motor frequency<
P436 Digital output hysteresis
S
0 ... 100 %
[ 10 ]
Difference between switch-on and switch-off point to prevent oscillation of the output signal.
P460 Time watchdog
S
0.0 / 0.1 ... 250.0 s
[ 10.0 ]
0.1 ... 250.0 = The time interval between the expected watchdog signals (programmable
function of digital inputs P420 – P425). If this time interval elapses without an
impulse being registered, a switch-off and error message E012 are actuated.
0.0 = Customer error: As soon as a high-low flank or a low signal is detected at a digital
input (function 18) the FI switches off with error message E012.