120 Subject to technical alterations BU 0200 GB
Parameter
[factory setting]
Setting value / Description / Note Device Supervisor
Parameter
set
P480 ... - 01
...
... - 12
Function Bus I/O In Bits
0 ... 72
[ -01 = 01 ]
[ -02 = 02 ]
[ -03 = 05 ]
[ -04 = 12 ]
[ -05...-12 = 00 ]
The Bus I/O In Bits are perceived as digital inputs. They can be set to the same functions (P420).
These I/O bits can also be used in combination with the AS Interface (SK 225E or SK 235E) or
the I/O extension (SK CU4-IOE or SK TU4-IOE).
[-01] = Bus I/O In Bit 0
[-02] = Bus I/O In Bit 1
[-03] = Bus I/O In Bit 2
[-04] = Bus I/O In Bit 3
[-05] = Bus I/O In Bit 4
[-06] = Bus I/O In Bit 5
[-07] = Bus I/O In Bit 6
[-08] = Bus I/O In Bit 7
[-09] = Flag 1
[-10] = Flag 2
[-11] = Bit 8 BUS control word
[-12] = Bit 9 BUS control word
The possible functions for the Bus In Bits can be found in the table of functions for the digital
inputs in parameter P420.
P481 ... - 01
...
... - 10
Function Bus I/O Out Bits
0 ... 39
[ alle 0 ]
The Bus I/O Out Bits are perceived as multi-function relay outputs. They can be set to the same
functions (P434).
These I/O bits can also be used in combination with the AS Interface (SK 225E or SK 235E) or
the I/O extension (SK CU4-IOE or SK TU4-IOE).
[-01] = Bus I/O Out Bit 0
[-02] = Bus I/O Out Bit 1
[-03] = Bus I/O Out Bit 2
[-04] = Bus I/O Out Bit 3
[-05] = Bus I/O Out Bit 4
[-06] = Bus I/O Out Bit 5
[-07] = Flag 1
[-08] = Flag 2
[-09] = Bit 10 BUS status word
[-10] = Bit 13 BUS status word
The possible functions for the Bus Out Bits can be found in the table of functions for the relay P434.
P482 ... - 01
...
... - 08
Standardisation Bus I/O Out Bits
-400 … 400 %
[ alle 100 ]
Adjustment of the limit values of the limit values of the Bus Out bits. For a negative value, the
output function will be output negative.
If the limit value is reached and the set values are positive, the output gives a High signal. If the
set values are negative, the signal is Low.
P483 ... - 01
...
... - 08
Hysteresis Bus I/O Out Bits
S
1 … 100 %
[ alle 10 ]
Difference between switch-on and switch-off point to prevent oscillation of the output signal.
NOTE:
For further details of the use of the Bus systems, please refer to Manual BU 0250.