5.6 Additional Parameters
BU 0200 GB Subject to technical alterations 125
Parameter Setting value / Description / Note Device Supervisor
Parameter
set
P533 Factor I
2
t-Motor
S
50 ... 150 %
[ 100 ]
The motor current for the I
2
t motor monitoring P535 can be weighted with the parameter P533.
Larger factors permit larger currents.
P534 ... - 01
... - 02
Torque-based disconnection limit
S P
25 ... 400 % / 401
[ all 401 ] ]
Via this parameter both the
drive [-01] and the generator [-02] switch-off value can be adjusted.
If 80% of the set value is reached, a warning status is set. At 100% switch-off is performed with
an error message.
Error 12.1 is given on exceeding the motor switch-off limit and E12.2 on exceeding the
generator switch-off limit.
[-01] = motor switch-off limit [-02] = generator switch-off limit
401 = OFF, means that this function has been disabled.