6 Error Messages
BU 0200 GB Subject to technical alterations 155
Anzeige in der
SimpleBox
Error
text in the Parameter Box
Cause
Remedy
Group Detail in
P700 / P701
E010
10.0 Telegram downtime / Bus off
24V int. CANbus
Data transfer is faulty. Check P513.
Check external bus connection.
Check bus protocol program process.
Check Bus master.
Check 24V supply of internal CAN/CANopen Bus.
Nodeguarding error (internal CANopen)
Bus Off error (internal CANbus)
10.2 External bus module
telegram time-out
Telegram transfer is faulty.
Check external connection.
Check Bus Protocol program process.
Check Bus master.
10.4 External bus module
initialisation failure
Check P746.
Bus module not correctly plugged in.
Check Bus module current supply.
10.1 External Bus module system
failure
Further details can be found in the respective additional
BUS operating instructions.
10.3
10.5
10.6
10.7
10.8 External module
communication failure
Connection fault / error in the external component
10.9 Missing module
Module entered in P120 is not available.
E011
11.0 Customer Unit ADU
(analog/digital converter
error)
Internal Customer Unit (internal data bus) faulty or disturbed
by radio emissions (EMC).
Check control terminals connection for short-circuit.
Minimise EMC interference through separate laying of
control and power cables.
Device and shielding must be well earthed.