EasyManua.ls Logo

Nortec RH - Page 25

Nortec RH
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Start Up | 22
Installation Check
Before turning on power to the RH inspect the installation to insure that it was carried out
correctly. Refer to, to RH Pre-Start Up Checklist on page 26, and to the chapter on installation.
Figure 23: Installation Check
Steam Line
- Adequate slope
- No restrictions
- no kinks (hose)
- Condensate
traps on long
runs
P Trap with
12 in (30 cm)
min drop
.
Fused
Disconnect
Correct
voltage /
amps / phase
per spec label.
On/Off
Controls
(Air Proving)
in series
between
terminal
1 and 2
10 ft (3 m) min.
Humidity Control
- Wired to Term 4.
- n series between
term 1 and 2.
location which
represents
humidified
space (no drafts,
not by door, not by
diffuser).
I
Modulating
On/Off
- in return duct or
Air Gap
Not Plastic Drain,
Not to sink.
High Limit
On/Off
- In series between
terminal1and 2
Modulating
- Wired to termina 4.
Mounting
- Unit Level
- Screws into
structural
member
Spec Label
4 ft (1.2 m) min.
Filter, bend or
any other
obstruction.
1/2 in line min to within 4 ft (1.2 m)
30-80 PSI
2 x duct height
from fan or
transition
2/3 duct
height
12 in.
(30 cm)
min.
Note: if a modulating control
is connected to the RH
then jumper J10 must
be removed.

Related product manuals