Start Up | 26
RH Pre-Start Up Checklist
Unit Serial #: _________________ No. of humidifiers: _______ Tag: _______________
Unit type: _______ __________ Voltage: ________V/_____ph
Cylinder type: Customer/Job: Address:
WATER QUALITY:
Well water F City water F Softened water F
HUMIDIFIER MOUNTING: (Clearances around the unit Acceptable Obstruction)
Level Front Clearance 36 in. F
STEAM LINE(S):
Material F Diameter / Size F
Slope up (min 2 in/ft) F Slope down (min 0.500 in/ft) F
Low point condensate traps F No hose kinks / Restrictions F
Type of Insulation
CONDENSATE LINE(S):
P Trap min 6 in or duct press + 2in F P Trap min 12 in drop F
WATER LINE:
1/2 in to within 4ft of unit F Water pressure: 30-80 psig F
DRAIN LINE:
Air gap within 3 ft of the unit F Diameter / Size F
CYLINDER:
Seated in drain valve and secured yes F no F
WIRING:
Wiring connections and connectors secured yes F no F
CONTROLS:
On / Off / Security loop devices working correctly yes F no F
Jumper J10 set to
Modulating (removed) F
Or
On/Off (installed) F
Control Location
High Limit Location
POWER:
Voltage, amp, fuse per Spec Label: yes F no F
Disconnect switch located close to humidifier yes F no F
Panel Number
Inspected by:
Date of inspection: ______/_______/______
Company: