D SERIES ELECTRIC FURNACE
FB0004
INSTALLATION AND USER MANUAL
IMPORTANT
: READ AND SAVE THESE INSTRUCTIONS.
MODELS: 21D10, 21D15, 21D18, 21D20, 21D23, 21D25 AND 21D27
M
A
D
E
I
N
C
A
N
A
D
A
F
A
B
R
I
Q
U
É
A
U
C
A
N
A
D
A
30042524B
12575216KHUEURRNH4XHEHFZZZGHWWVRQFD

Other manuals for Nortron D SERIES

Questions and Answers

  • A
    alejandro61Sep 3, 2025
    How to troubleshoot Nortron D SERIES that will not start?
    • M
      Miguel AlvarezSep 4, 2025
      To troubleshoot why your Nortron Furnace won't start, first turn the thermostat to its highest setting. Check if there is 24V present between terminals C and W. If there is, the thermostat is working, and the fault lies within the furnace itself. If there is no voltage, the problem is with the thermostat or its connecting wires.
  • R
    Richard ChanSep 18, 2025
    Why thermostat must be set much higher than desired temperature on Nortron Furnace?
    • R
      Rachel JonesSep 18, 2025
      If the thermostat on your Nortron Furnace needs to be set much higher or lower than the desired house temperature, the thermostat may not be leveled or may be out of calibration.
  • M
    morganmartinezSep 16, 2025
    Why is the motor on my Nortron Furnace going on and off in short cycles?
    • B
      baileyjamieSep 16, 2025
      If the motor in your Nortron Furnace is cycling on and off too quickly or slowly, the heat anticipator in the thermostat may be incorrectly set or defective.
  • J
    juliesalinasSep 14, 2025
    What to do if elements are on, but motor does not run on Nortron D SERIES?
    • F
      fcurrySep 14, 2025
      If the elements are on but the motor isn't running in your Nortron Furnace, the issue may stem from the motor or capacitor, an open contact in the SPEED SELECTOR switch, or a problem with the electronic control.
  • Z
    Zachary CruzSep 13, 2025
    Why does the thermal cut-out open on my Nortron Furnace?
    • D
      David HansonSep 13, 2025
      The thermal cut-out in your Nortron Furnace may open if airflow is reduced due to blocked ductwork or very dirty filters.
  • J
    John JacobsSep 12, 2025
    Why does my Nortron D SERIES motor run continuously?
    • B
      Brian NavarroSep 12, 2025
      If the motor in your Nortron Furnace runs continuously, it could be due to thermostat wires being incorrectly attached to the furnace.
  • A
    alex89Sep 9, 2025
    Why Nortron D SERIES will not turn on?
    • S
      Shaun JonesSep 9, 2025
      If your Nortron Furnace will not turn on, potential causes include issues with the thermostat, an open circuit breaker or fuse, problems with the motor or capacitor, an open contact in the SPEED SELECTOR switch, a faulty electronic control, or the transformer.
  • L
    Lance CabreraSep 7, 2025
    Why does the breaker on my Nortron Furnace keep tripping?
    • K
      kimberlypotterSep 7, 2025
      If the breaker on the front panel of your Nortron Furnace trips, it indicates an overcurrent on the heating element. Reset the breaker. If the problem continues, it is recommended to call an electrician.
  • S
    Steven HortonSep 5, 2025
    What to do if Nortron D SERIES Furnace will not turn off?
    • T
      Tammy SmithSep 5, 2025
      If your Nortron Furnace won't turn off, set the thermostat to its lowest setting. Check if there is still 24V between terminals C and W. If the furnace continues to run with no voltage, the thermostat is opening properly, and the problem is in the furnace. If voltage is present, the fault is in the thermostat or its wiring.
  • A
    ashley05Aug 21, 2025
    Why Nortron D SERIES is not producing enough heat?
    • M
      Mercedes HumphreyAug 21, 2025
      If your Nortron Furnace isn't producing enough heat, it could be due to several reasons: * One or more defective heating elements or relays. * The HEAT ACTIVATION switch is set to the LOW position. * Safety limits opening due to duct obstruction or dirty filters restricting airflow. * A defective or incorrectly wired two-stage or outdoor thermostat. * Lack of enough cold air returns in the house.

Summary

General Requirements and Specifications

Operating Options

Breakers

Installation Notes

Cold Air Return

Details on attaching the cold air return duct to the furnace sides, rear, or bottom.

Electrical Wiring - Power Supply

Instructions for connecting the power supply, emphasizing proper grounding and wire gauge.

Connecting and Adjusting the Low Voltage Thermostat

Guide for wiring thermostat and setting the heat anticipator for optimal furnace operation.

Use in Mobile Homes

Using Optional Equipment

Two-Stage or Outdoor Thermostat

Guidance on connecting and using two-stage or outdoor thermostats with the furnace.

Air Conditioning

Information on integrating air conditioning with the furnace, including coil placement and airflow.

Electronic Air Cleaners and;or Powered Furnace Humidifiers

Details on using an adapter kit to power 120V air cleaners and humidifiers.

Interlock Connection

Procedure for connecting the electric furnace with other devices like wood furnaces.

Wiring Diagrams

21 D10 Model Wiring

Detailed wiring diagram for the Nortron D Series 21D10 electric furnace.

21 D15 Model Wiring

Detailed wiring diagram for the Nortron D Series 21D15 electric furnace.

21 D18 & 21 D20 Models Wiring

Detailed wiring diagrams for Nortron D Series 21D18 and 21D20 electric furnaces.

21 D23 & 21 D25 Models Wiring

Detailed wiring diagrams for Nortron D Series 21D23 and 21D25 electric furnaces.

21 D27 Model Wiring

Detailed wiring diagram for the Nortron D Series 21D27 electric furnace.

Service Parts

Maintenance

Troubleshooting